NBS Source
I'm a manufacturer

QIO850 Quad Input/ Output Module

Verified by manufacturer 3 months ago

Johnson Controls Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Quad input/ output module.

Jump to:
BOS
Website

Application

Use only with MZX Fire Alarm Controllers. Indoor application only.

Description

The module provides four monitored inputs and four potential free relay changeover outputs.


The outputs are monitored with parallel contacts of

the relays. The outputs can be connected to an Auxiliary

Voltage source and its voltage can be monitored.


Additionally, all the outputs can be connected to the HVR800, for switching high power galvanic isolated

loads. For more details refer to the HVR800 documentation.


The module has an integral loop isolator. If this activates

a yellow LED illuminates. The activation remains in place until the short is removed.

The digital input monitoring and isolator functions

are both configurable.


Features and benefits:

Input Circuit:

  • EOL terminator: nominal 3.3 Kilo Ohms
  • Alarm resistor: nominal 0.68 Kilo Ohms
  • Open and Short circuit detection can be set to:
  • Maximum cable resistance: 50 Ohms
  • Maximum cable length: 200 m (standard cable J-Y(ST)Y nx2x0.8)

Output Circuit (Relay Contact):

  • Nominal switching capacity 2 A 30 VDC (resistive load)
  • Maximum switching power 60 W, 125 VA (resistive load).

Auxiliary Voltage Input:

  • Auxiliary voltage 24 VDC max 55 VDC (Threshold voltage for auxiliary voltage fault indication: 18 VDC ± 1 VDC)
  • Auxiliary voltage 48 VDC max 55 VDC (Threshold voltage for auxiliary voltage fault indication: 36 VDC ± 2 VDC)

General information

Color

Clear

Finish

Acrylic

Material

Plastic

Shape

Rectangle

Length

49 mm

Guidance for specification option:

Depth

Width

103 mm

Height

134 mm

Warranty description

Three year

Uniclass

Pr_75_80_30_28 Fire alarm input and output modulesPrimary

Specification data - Fire alarm input and output modules

Standards

To EN 54-17, EN 54-18 EN 50130-4 and EN 61000-6-3.

Device type

Quad Input/ Output Module.

Mounting arrangement

Back box surface mounted.

DIN rail.

Enclosure

-

Ingress protection (minimum)

557.201.410 IP66 Housing for Quad I/O Modules.

Colour

Clear.

Operating temperature

–25 to +70°C.

RelativeHumidity

Up to 95 % non condensing.

Sustainability data

Contains Red List materials

No

Country of material origin

Czechia

Country of product manufacture

Czechia

Material

Plastic

Manufacturing plant location

Expected Life

Ten year

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

QIO850 CPR

Literature

557.201.410 IP66 Housing for Quad IO Modules

557.201.410 IP66 Housing for Quad IO Modules