NBS Source
I'm a manufacturer

MIM800 Mini-Input Module

Verified by manufacturer 4 months ago

Johnson Controls Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Addressable mini input module.

Jump to:
BOS
Website

Application

The MIM800 can be mounted in any electrical enclosure with sufficient depth to accommodate the MIM800 and field contacts monitored by the IN+ and IN- terminals, ie, no field wiring. The remote LED (if required, not supplied) must be located within the same electrical enclosure.


Description

The MIM800 Addressable Mini Input Module supervises one circuit of voltage-free contacts, such as outputs from extinguishing systems, ventilation controls, etc, and transmit the state to the Tyco MX Control and

Indicating Equipment (CIE).


Both devices can be programmed to supervise either

normally-open or normally-closed contacts. The default

MIM800 configuration is to supervise normally-open

contacts. The MIMs can be programmed to

supervise:

  • One circuit of multiple normally-open contacts, with
  • short circuit alarm.
  • One circuit of multiple normally-closed contacts, with open circuit alarm.
  • One circuit with a single normally-open contact, closing for alarm, with fault detection for short circuit. This requires a 100 ohm resistor in series with the alarm contact and appropriate programming at the MX CIE.

Interrupt operation can be enabled for fast transmission of a change-of-state to the MX CIE.


The contacts supervised must be voltage free. Do not connect the input to non isolated equipment or to the inputs of other MX devices.


The MIM800 has a output suitable for connection to a

co-located LED. No series resistor is required. This can be

controlled by the CIE.


Features and benefits:

  • Single monitored input
  • Programmable configuration
  • Monitor multiple n/o contacts
  • Monitor multiple n/c contacts
  • Controllable output for led
  • Compact footprint.


The unit must be housed in a suitable enclosure immediately adjacent to the contacts being monitored. It can be fixed to a surface or mounted with a screw through the tab and a 8.5 mm standoff. The unit is for internal use only unless housed in a weatherproof enclosure.


The unit is shipped with a default (invalid) address of 255 and must be set to the correct loop address using the

850EMT or MX Service Tool.

General information

Color

Black

Finish

Matt

Material

Plastic

Shape

Rectangle

Length

57 mm

Guidance for specification option:

Depth

Width

48 mm

Height

13 mm

Warranty description

Three year

Uniclass

Pr_75_80_30_28 Fire alarm input and output modulesPrimary

Specification data - Fire alarm input and output modules

Device type

Mini-Input Module.

Mounting arrangement

Surface.

Screw mounted though tab with standoff.

Enclosure

-

Material

Plastic.

Colour

Black.

Operating temperature

–25 to +70°C.

RelativeHumidity

10–95% (non condensing).

Voltage

20–40 Vdc.

Manufacturer guidance

  • Quiescent Current 275 μA (typical)
  • Alarm State Current 2.8 mA
  • Maximum MIM800 / Loop 200/250.

Sustainability data

Contains Red List materials

No

Country of material origin

Czechia

Country of product manufacture

Czechia

Material

Plastic

Manufacturing plant location

Expected Life

Ten year

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

MIM800 CPR

Similar products from Johnson Controls

BDM800 Beam Detector Module With Cover

BDM800 Beam Detector Module With Cover

CIM800 Contact Input Module With Cover

CIM800 Contact Input Module With Cover

DIM800 Detector Input Module With Cover

DIM800 Detector Input Module With Cover

IF800Ex MZX Digital Addressable Interface Module Assembly

IF800Ex MZX Digital Addressable Interface Module Assembly

QIO850 Quad Input/ Output Module

QIO850 Quad Input/ Output Module

QRM850 Quad Relay Module

QRM850 Quad Relay Module

RIM800 Relay Interface Module With Cover

RIM800 Relay Interface Module With Cover

SNM800 Sounder Notification Module With Cover - Sounder Notification Module

SNM800 Sounder Notification Module With Cover - Sounder Notification Module

TM520 Timer Module–Non Addressable

TM520 Timer Module–Non Addressable

TSM800 - Door Control Module

TSM800 - Door Control Module