A single-component, water-based, thin-film, intumescent fire protection coating.

Jump to:
+44 (0)1204 521771 Website

Application

  • Civil infrastructure.
  • Designed for application by airless spray to provide fire resistance for periods of up to 120 minutes on structural steel.
  • For use in internal dry controlled environments without topcoat. (C1 according to ISO 12944-2) and external urban or uncontrolled internal environments with topcoat (C3 according to ISO 12944-2).

Description

Intended for use on interior and exterior exposed structural steel substrates, FIRETEX® FX5090 water-based intumescent coating is designed to meet the highest performance, aesthetic, and environmental demands of today's commercial construction industry with ratings up to two hours.

Its visually appealing finish allows architects use of exposed steel as a design element - resulting in an aesthetic and decorative final appearance.

Features and benefits:

  • Provides up to two hours' fire protection.
  • Single component.
  • Aesthetic finish.
  • Impact resistance.
  • Outstanding application characteristics.
  • Does not contain TCEP.
  • UL Classified for exterior use (when top coated with Pro Industrial Waterbased Acrolon 100 per the appropriate UL Design).

General information

Color

White

Finish

Matt

Material

Water-based

Shape

Formless

Length

Bespoke

Width

Bespoke

Height

Bespoke

Uniclass

Pr_35_31_68_43 Intumescent protective coatingsPrimary

CAWS

G10/660 Shop plus site painting

M61/110 On-site coating to primed steel

M61/120 On-site coating to existing steel

G10/650 Site painting

SKU Code

FX5090

Specification data - Intumescent protective coatings

Classification data

Composition

Water-based.

Manufacturer guidance

Cleaner/ thinner: water.

Colour

White.

Standards

Independently fire tested and approved to major European and national
standards including.
EN 13381-8 (ref: ETA 23/0321);
CE Marking Number 2821-CPR-0349;
Tested to BS 476-20/21 (UL Certificate BS-RC-0018);

Guidance for specification option:

Other standards include:

  • Switzerland VKF Certification No. 31872;
  • German ABg Z-19.51-2694;
  • Australia AS4100 Certification;
  • Lithuania GTC Certification: GTC 100830;
  • Singapore SETSCO Certificate of Conformity: FSP-2024-1488.

Tested and assessed in accordance with the ASFP Yellow book 5th Edition for cellular beam protection.

LEED v4 and 4.1 Attestation.

WELL Building Standard Attestation.

Complies with German AgBB (when tested in accordance with report 392-2022-00430904_D_EN)

Primer

Not required.
Required.

Guidance for specification option:

Several primers have been approved for use under this product. Consult manufacturer for details and insert requirements.

Must not be applied directly to galvanized steel and zinc rich primers.

Top coat

Required.

Guidance for specification option:

  • If it can be guaranteed that application and subsequent in-service conditions will be in a C1 environment as defined in BS EN ISO12944-2:2017, then no topcoat is required.
  • For any other situation a topcoat must be applied, consult manufacturer for advice and insert requirements.

Not required.

Application method

Airless spray or brush.

Coverage

Theoretical:
Airless spray: 0.71 m²/kg (1.0 m²/L).
Brush: 1.64 m²/kg (2.3 m²/L).

Volume solids

To ASTM-D2697-03, 69% ±3%.

VOC content

<25 g/L (EPA method 24).

Drying time

At +15°C: to touch: 3 hours; to recoat: 6 hours.
At +23°C: to touch: 1½ hours; to recoat: 4 hours.

Density

1.4 kg/L.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Water-based
Carbon dioxide equivalent

Carbon dioxide equivalent, as defined in BS EN 15804

Certified

Stage
Normalised unit (kg CO₂ eq/kg)
Declared unit (kg CO₂ eq/kg)
Stage:A1–A3 ('Production stage')
Normalised unit : 2 (kg CO₂ eq/kg)
Declared unit : 2.00

Lower emissions

Recyclability

0

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Product certifications

Product certifications

EPD

EPD

FX5000 EPD Certificate

Literature

Steel Protection FIRETEX® FX5090 Product Data Sheet

Steel Protection FIRETEX® FX5090 Product Data Sheet

Similar products from Sherwin-Williams

Fire Protection FIRETEX® FX1003 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX1003 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX1007 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX1007 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX2003  - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX2003 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX2007 - Fire Protection

Fire Protection FIRETEX® FX2007 - Fire Protection

Fire Protection FIRETEX® FX5062 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX5062 - Thin-film Intumescent Coating for Steel

Fire Protection FIRETEX® FX6002 - Ultra Fast-Drying Intumescent Coating

Fire Protection FIRETEX® FX6002 - Ultra Fast-Drying Intumescent Coating

Fire Protection FIRETEX® FX6010 - Rapid Curing Intumescent Coating

Fire Protection FIRETEX® FX6010 - Rapid Curing Intumescent Coating

Fire Protection FIRETEX® FX9500 - Epoxy Intumescent Coating for Steel

Fire Protection FIRETEX® FX9500 - Epoxy Intumescent Coating for Steel

Fire Protection FIRETEX® Platinum - Epoxy-based Intumescent Coating

Fire Protection FIRETEX® Platinum - Epoxy-based Intumescent Coating