Verified by manufacturer 4 months ago
UR002 - rated steam production: 2 kg/h
Watermark
Certificate type
Resistive elements humidifiers designed to generate safe steam humidification for duct or in-room. Reliable and precise technology for high-tech applications.
Designed to generate safe steam humidification for duct or in-room, in applications where the priority is hygiene, such as research laboratories or the agriculture and food industry.
Resistive elements humidifiers designed to generate safe steam humidification for duct or in-room. Reliable and precise technology for high-tech applications. Steam production is modulated with the highest precision, using any feedwater.
The features of steam humidification make this technique the preferred solution in applications where the priority is hygiene, such as research laboratories or the agriculture and food industry: steam is in fact completely aseptic and does not carry solid particles, an intrinsic quality that is assured without needing to treat the feedwater.
Features and benefits:
Control features:
Features common to both models:
Process model:
A modular and flexible solution that represents the basis of the electric heater humidifier range, Incoloy® 825 heating elements allow operation in complex conditions, even when feedwater quality is not controlled. As per common features above plus:
Titanium model:
The pinnacle of this family of cutting-edge humidifiers. The unit can operate on any type of treated water, even extremely aggressive water with a conductivity below 1 μS/cm and softened down to 0°fH. (the titanium heating elements are completely resistant to corrosion). As per common features above plus:
Certifications:
CE, ETL (UL998), TÜV and EAC.
Color | White |
Finish | Galvanized Guidance for specification option: Housing. |
Material | Metal Guidance for specification option: Housing (galvanized). |
Shape | Rectangle |
Length | 365 mm 690 mm 876 mm |
Width | 275 mm 445 mm Manufacturer guidanceUnit depth. |
Height | 712 mm 888 mm |
Warranty description | Two year Guidance for specification option: Warranty for materials (from the manufacture date, excluding consumables). |
Uniclass |
Electrical supply type | Single phase, 230 V a.c., 50/ 60 Hz (D).Manufacturer guidanceVoltage: 10 to -15%. Other voltages available on request, consult manufacturer for details. |
Steam source | Resistive element. |
Material | Galvanized metal housing. |
Access doors for maintenance | Manufacturer's standard. |
Accessories | None.DP/*R0 lance for duct (standard).DP/*RU lance for duct (high capacity).DP/*RH lance for duct (high efficiency).SDP steam nozzle, 12 mm hole.SDP steam nozzle, 22 mm hole.SDP steam nozzle, no hole (to be drilled).Hoses.Guidance for specification option: Consult manufacturer for options and insert requirements. Probe - DPW* wall sensor.Probe - DPP* sensor for industrial environments.Probe - DPD* duct sensor.Probe - ASET* temperature sensor for steam baths.Fan blower, VS*.Fan blower, VR*.Manufacturer guidancePlastic. Up to 15 kg/h. Steam inlet suitable for 22 and 30 mm diameter. |
Model | Process (0). Guidance for specification option: A modular and flexible solution that represents the basis of the electric heater humidifier range, Incoloy® 825 heating elements allow operation in complex conditions, even when feedwater quality is not controlled. Titanium (1). Guidance for specification option: The world’s only humidifier with titanium heaters, represents the pinnacle of this family of cutting-edge humidifiers. The unit can operate on any type of treated water, even extremely aggressive water with a conductivity below 1 μS/cm and softened down to 0°fH. (the titanium heating elements are completely resistant to corrosion). |
Dimensions | 365 x 275 x 712 mm. Manufacturer guidanceLength x width (depth) x height. |
Weight | 26 kg. |
Network type | Modbus®. Guidance for specification option: Standard. BacNET. Guidance for specification option: Standard. BacNET Ethernet. Guidance for specification option: Standard. Modbus Ethernet. Guidance for specification option: Standard. LON. Guidance for specification option: Requires a gateway. |
Steam | Rated production: 2 kg/h. |
Power consumption | 2 kW. |
Connections | Steam: 30 mm diameter. |
Pressure | Outlet pressure limits: 0–1500 Pa. |
Conditions | Operating: 1 to 40°C, 10–60% relative humidity. |
Ingress protection | IP20. |
Water | Fill: |
Fan | One blower, type VSDU0A; rated air flow: 288 m³/h. Guidance for specification option: Power supply: 24 V a.c. Rated power: 46 W. |
Heater | One. |
Platform | Compatible | Version |
---|---|---|
- | 1 |