Verified by manufacturer 4 months ago
FLE05 - rated steam production: 4.8–5.2 kg/h
Watermark
Certificate type
Declare
Certificate type
Steam humidifiers which consist of a basic model that can be expanded to create an individual humidification solution.
Applications include:
Steam humidifiers which consist of a basic model that can be expanded to create an individual humidification solution suitable for all requirements.
Features and benefits:
Certifications:
VDE and GS certification; CE- and EAC-compliant.
Color | White Silver |
Finish | Powder-coated |
Material | Stainless steel |
Shape | Other |
Length | 320 mm 355 mm 420 mm |
Width | 540 mm 580 mm 640 mm 1130 mm 1170 mm |
Height | 535 mm 695 mm 750 mm 785 mm |
Warranty description | One year Guidance for specification option: Materials warranty (from the manufacture date, excluding consumables). |
Uniclass |
Electrical supply type | Three phase, 380–415 V a.c., 50/ 60 Hz. |
Steam source | Electrode boiler (immersed electrodes). |
Material | Stainless steel. |
Access doors for maintenance | Manufacturer's standard. |
Accessories | Not required.Standard manifolds.Guidance for specification option: Lances for duct (HVAC). Fan blower, VU10 up to 10 kg/h.Guidance for specification option: Fan blower for room (HVAC). Fan blower, VU30 up to 30 kg/h.Guidance for specification option: Fan blower for room (HVAC). Steam hose.Fogmaker for steam bath.Guidance for specification option: Wellness and SPA. Steam jet nozzle for steam bath.Guidance for specification option: Wellness and SPA. Remote display for steam bath.Guidance for specification option: Wellness and SPA. Temperature sensor for steam bath.Guidance for specification option: Wellness and SPA. |
Dimensions | 540 x 535 x 320 mm. Manufacturer guidanceW x H x L. |
Weight | 16 kg. |
Network type | Modbus RTU. BACnet. |
Steam | Rated production: 4.8–5.2 kg/h. |
Power consumption | 3.6–3.9 kW. Guidance for specification option: Nominal current: 5.4 A. |
Connections | Steam diameter: HVAC - Ø25 SPA - Ø40. |
Pressure | Outlet pressure limits: 0–1500 Pa. |
Cylinders | Standard cleanable cylinder. Split cylinder. Guidance for specification option: Easy to open and can be cleaned without using chemicals. SuperFlush and HyFlush. Guidance for specification option: Cylinder flushing device. HyCool. Guidance for specification option: Integrated waste water cooling. Manufacturer guidanceOne cylinder. |
Conditions | Operating: 5 to 40°C, to not exceed 80% relative humidity. |
Ingress protection | IP20. |
Model | FLE-T (HVAC) - Electrode. Guidance for specification option: Equip HygroMatik FlexLine with the power you need for optimum humidification. Performance classes with steam output from 5 kg/h to 130 kg/h are selectable in 6 housing sizes. In addition, individual performance adjustments can be programmed both at the factory and on site. FLE-TSPA (Wellness/ SPA) - Electrode. Guidance for specification option: Equip HygroMatik FlexLine with the power you need for optimum humidification. Performance classes with steam output from 5 kg/h to 130 kg/h are selectable in 6 housing sizes. In addition, individual performance adjustments can be programmed both at the factory and on site.
|
Water | Fill: |
Fan | One blower, type VU10. Guidance for specification option: Power supply: 220-240V / 1 / N. Rated power: 26 W. Sound level: 49 dB(A) (at 1 m distance). Manufacturer guidanceSteam outlet adapter Ø25 mm to Ø40 mm needed. |
Platform | Compatible | Version |
---|---|---|
- | 1 |