UR - heaterSteam - Steam Humidifier Range
UR - heaterSteam - Steam Humidifier Range
UR - heaterSteam - Steam Humidifier Range

Verified 25 days ago

CAREL

Verified 25 days ago

CAREL

Verified 25 days ago

CAREL
Summary
Resistive elements humidifiers designed to generate safe steam humidification for duct or in-room. Reliable and precise technology for high-tech applications.
Product certifications
Digital objects
-
-
Color
White
-
-
Finish
Galvanized
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
365 mm, 690 mm, 876 mm
-
-
Width
275 mm, 445 mm
-
-
Height
712 mm, 888 mm
-
-
Warranty description
Two year
-
-

Specification

Electrical supply type
Single phase, 230 V a.c., 50/ 60 Hz (D).
-
-
Steam source
Resistive element.
-
-
Material
Galvanized metal housing.
-
-
Access doors for maintenance
Manufacturer's standard.
-
-
Accessories
None., DP/*R0 lance for duct (standard)., DP/*RU lance for duct (high capacity)., DP/*RH lance for duct (high efficiency)., SDP steam nozzle, 12 mm hole., SDP steam nozzle, 22 mm hole., SDP steam nozzle, no hole (to be drilled)., Hoses., Probe - DPW* wall sensor., Probe - DPP* sensor for industrial environments., Probe - DPD* duct sensor., Probe - ASET* temperature sensor for steam baths., Fan blower, VS*., Fan blower, VR*.
-
-

Additional properties

Model
Process (0)., Titanium (1).
-
-
Dimensions
365 x 275 x 712 mm.
-
-
Weight
26 kg.
-
-
Network type
Modbus®., BacNET., BacNET Ethernet., Modbus Ethernet., LON., KONNEX.
-
-
Steam
Rated production: 2 kg/h.
-
-
Power consumption
2 kW.
-
-
Connections
Steam: 30 mm diameter.
Water fill: 3/4”G male.
Water drain: 40 mm.
-
-
Pressure
Outlet pressure limits: 0–1500 Pa.
-
-
Conditions
Operating: 1 to 40°C, 10–60% relative humidity.
Storage: -10 to 70°C, 5–95% relative humidity.
-
-
Ingress protection
IP20.
-
-
Water
Fill:
· Temperature limits: 1 to 40°C.
· Water pressure limits: 0.1 to 0.8 MPa (1 to 8 bar).
· Instant flow rate: 1.1 L/m.
· Total hardness: 5 to 40°fH.
· Conductivity limits: 75 to 1250 μS/cm.
Drain:
· Temperature: <100°C.
· Instant flow rate: 5 L/m (50 Hz); 9 L/m (60 Hz).
-
-
Fan
One blower, type VSDU0A; rated air flow: 288 m³/h.
-
-
Heater
One.
-
-