NBS Source
I'm a manufacturer

MCP820 Indoor Callpoint With Isolator

Verified by manufacturer 13 days ago

Johnson Controls Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Generation 6 MX detection range manual call point.

Jump to:
BOS
Website

Application

Indoor Application only

Description

The MCP820 Addressable Manual Call Point is suitable for indoor applications. As supplied, it is suitable for flush mounting. A surface mounting back box is available separately. The MCP820 is designed to monitor and signal the condition of a switch contact that is operated by breaking a plastic coated glass frangible element (flexible plastic option available). Any change in the status of the switch is immediately communicated to the Tyco MX Control and Indicating Equipment (CIE).


The MCP820 has an integral short-circuit isolator for monitoring the addressable loop wiring. The integral LED indicator is normally off. When the frangible element is broken, an alarm is registered and the LED will illuminate red. If a section of the loop wiring adjacent to the MCP820 is shorted, the built-in shortcircuit isolator trips, isolating the shorted section and the LED is illuminated yellow. The status remains until the short is removed.


Features and benefits:

  • Compatible with MX Addressable Loop on VIGILANT MX1 and VIGILANT MX4428 panels
  • Integral Short Circuit Isolator
  • LED Status Indication
  • EN54-11 Certification
  • Compact, Modern Styling
  • Test Key for Fast Testing
  • ActivFire Listing afp-2874 (EN 54-11).

General information

Color

Red

Finish

Semi-gloss

Material

Acrylonitrile butadiene styrene (ABS)

Shape

Other

Length

59.9 mm

Guidance for specification option:

Depth

Width

89 mm

Height

93 mm

Warranty description

Three year

Uniclass

Pr_75_80_30_50 Manual call pointsPrimary

CAWS

W90/336 Manual call points

Specification data - Manual call points

Standard

To EN 54-11.

Frangible element

515.001.025 Frangible Glass Element.

Integral red visual indicator

Required.

Environmental category

Indoor.

Mounting

Surface.

Protective covers

SU0615 Transparent Hinged Cover.

Power source

Loop.

Manufacturer guidance

  • Loop Voltage: 20–40 Vdc
  • Quiescent Current 280 μA.
  • Alarm State Current 2.8 mA.
  • Max. MCP820 / Loop 200/250.

Operating temperature

–10 to +55°C.

Ingress protection

IP24D.

Sustainability data

Contains Red List materials

No

Country of material origin

Romania

Country of product manufacture

Romania

Material

Acrylonitrile butadiene styrene (ABS)

Manufacturing plant location

Expected Life

Ten year

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

MCP820 CPR

Literature

514.800.611 MCP820 Indoor Callpoint With Isolator

514.800.611 MCP820 Indoor Callpoint With Isolator

Similar products from Johnson Controls

CP840Ex Break Glass Callpoint

CP840Ex Break Glass Callpoint

EX II 2 GD Dust Approved and Increased Safety (EExemd) Resettable Manual Alarm Callpoint

EX II 2 GD Dust Approved and Increased Safety (EExemd) Resettable Manual Alarm Callpoint

MCP830 Outdoor Callpoint With Isolator

MCP830 Outdoor Callpoint With Isolator