Verified by manufacturer today
Single No Smoke Seals
Certifire Certificate
Certificate type
IFCC
Certificate type
IFCC
Certificate type
smas WORKSAFE
Certificate type
Vertical active fire and smoke curtain barrier providing 120 minutes integrity and up to 85 minutes radiation control, tested to BS 8524-1 and installed to BS 8524-2.
Vertical active fire and smoke curtain barrier suitable for applications requiring BS 8524-compliant smoke control and life-safety performance, including protected means of escape, atria, lobbies, reception areas, corridor separation, openings in fire-resisting walls, boundary protection, escalators, stairwells, lift shafts and lift lobbies.
Commonly specified within hospitals and healthcare environments, schools and universities, hotels, high-rise buildings, offices, retail developments, stadia, museums and galleries, as well as transport infrastructure such as train stations and airports. Also suitable for warehouses, factories, nurseries, shopping centres, restaurants, and defence or custodial environments where certified fire and smoke containment is critical.
The Flameshield 8524 (S) Fire and Smoke curtain is designed for multiple applications such:
The Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier is an electrically operated, gravity fail-safe fire and smoke control system developed specifically to meet the life-safety requirements of BS 8524-1, with installation in accordance with BS 8524-2. The system provides 120 minutes fire integrity and up to 85 minutes radiation performance at 15 kW/m², supporting occupant tenability and protected means of escape strategies.
The barrier assembly incorporates a carbon steel barrel and integrated 24 V d.c. electric motor, with a high-performance flexible fire curtain fabric capable of withstanding temperatures in excess of 1000°C. Barrel deflection performance complies with BS 6323-5, ensuring structural stability during deployment. A two-section T-profile bottom rail delivers smooth, controlled descent and reliable gravity fail-safe operation in the event of power or system failure.
The Flameshield 8524 (S) includes internal battery back-up, enabling continued operational readiness during mains power interruption. A two-stage closing sequence with split-drop and timed delay options supports phased evacuation and enhanced safety management in occupied buildings.
Designed to support architectural intent as well as performance, the system can be concealed above ceiling lines, with end plates, guides and head boxes available in specialist RAL finishes, allowing seamless integration with interior design schemes.
A comprehensive range of ancillary safety equipment is available, including egress switches, access switches, obstruction detection, and heat and smoke activation, all fully tested to Annex H of BS 8524-1. Optional audible and visual warning systems, including voice warning devices, can be specified to enhance occupant awareness during curtain deployment.
The Flameshield 8524 (S) is fully compliance-tested, offers low maintenance requirements, and is capable of full reset following fire testing without the need for specialist engineer attendance.
Independent testing and approval has been carried out by Warrington Fire Research Centre and Exova, including:
Associated Warrington test references include WF 341175 (deflection), WF 347098 (smoke), WF 399170 (motor performance) and WF 399421 (surface spread of flame to BS 476-6 and BS 476-7).
Features and benefits:
Color | Other Manufacturer guidanceAll RAL colours available. |
Finish | Powder-coated Guidance for specification option: Powder coated to C3 class. Additional corrosivity classes available to C3H through treatment and application of specialist primer. |
Material | Carbon steel |
Shape | Rectangle |
Length | Bespoke |
Width | 10000 mm |
Height | 10000 mm Guidance for specification option: Overall width and height restrictions may apply. |
Warranty description | One year Guidance for specification option: Extended warranty available on application. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
SKU Code | FS 8524S |
Classification data | |
Standards | |
Barrier assemblies | To BS 8524-1, BS EN 1634-1 and BS 1634-3. |
Test standards | Vertical, horizontal and angled to BS EN 1634-1. |
Third-party certification | IFCC 1542 and IFCC 3425. Warrington Fire Report 340986. |
Size | Manufacturer guidanceMaximum size (w x h): 5000 x 6000 mm. (32 m²). Insert requirements. |
Performance | |
Pressure and impact | Tested to BS 5234-1 (Clause 5.2 BS 8524-1) Warrington Test number WIL 403113 Issue 3. |
Durability class | C1. |
Smoke containment | No smoke seals. |
Fire resistance | 120 minutes integrity classified to EW60. Manufacturer guidanceTo BS 476-6 and BS 476-7. |
Reaction to fire | To BS 476-6 and BS 476-7. |
Deployment | Immediate deployment from receipt of alarm signal. Split and delay drop facilities with timed hold. |
Activation | Specialist panel with internal battery back up and modified motor. Activation on receipt of relevant alarm signal. |
Accessories | Partial Drop. Guidance for specification option: The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes Emergency Retract. Guidance for specification option: The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available. BMS Interface. Guidance for specification option: The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed. Single Photo Cell. Guidance for specification option: Tested and Passed by Exova to BS 8524-1 Annex H Audio / Visual / Spoken Warning Unit. Guidance for specification option: The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An Audio / Visual / Spoken warning unit can be interfaced with this using power supplied by the primary / secondary source or via an external source. Egress switches. Access switches. |
Radiation | 85 minutes at 15 kW/m². |
Fabric | Fire rated fabric 0.54 mm thick stainless steel wire reinforced, aluminium pigmented and fire retardant polymer. Guidance for specification option:
|
Barrel | Carbon steel tube. Guidance for specification option: Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards. |
Colour and finish | Manufacturer guidanceConsult manufacturer and insert requirements. Available in any RAL colour. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Manufacturing plant location | |
Material | Carbon steel |
Expected Life | Ten year Guidance for specification option: Lifetime under BS 8524-2. Manufacturer guidanceLifetime under BS 8524-2. |
This BIM object has been authored to meet the requirements of the
Find out more about the
| Platform | Compatible | Version |
|---|---|---|
| - | 1 | |
| - | 1 |
Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested
Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain
Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested
Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Fire and Smoke Curtain
Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested
Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain
Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain