Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire and Smoke Curtain

Verified by manufacturer today

Single No Smoke Seals

A1S Group Variant:
Product certifications:
  • Certifire Certificate

    Certifire Certificate

    Certificate type

  • IFCC

    IFCC

    Certificate type

  • IFCC

    IFCC

    Certificate type

  • smas WORKSAFE

    smas WORKSAFE

    Certificate type

Vertical active fire and smoke curtain barrier providing 120 minutes integrity and up to 85 minutes radiation control, tested to BS 8524-1 and installed to BS 8524-2.

Jump to:
BOS
+44 (0)1204 383839 Website

Application

Vertical active fire and smoke curtain barrier suitable for applications requiring BS 8524-compliant smoke control and life-safety performance, including protected means of escape, atria, lobbies, reception areas, corridor separation, openings in fire-resisting walls, boundary protection, escalators, stairwells, lift shafts and lift lobbies.

Commonly specified within hospitals and healthcare environments, schools and universities, hotels, high-rise buildings, offices, retail developments, stadia, museums and galleries, as well as transport infrastructure such as train stations and airports. Also suitable for warehouses, factories, nurseries, shopping centres, restaurants, and defence or custodial environments where certified fire and smoke containment is critical.

The Flameshield 8524 (S) Fire and Smoke curtain is designed for multiple applications such:

  • Protected means of escape.
  • Atriums.
  • Lobbies.
  • Receptions.
  • Openings in walls.
  • Egress.
  • Corridor separation.
  • Boundary protection.
  • Escalators.
  • Stairs.
  • Lifts and lift lobbies.
  • Hospitals.
  • Schools.
  • Hotels.
  • High Buildings.
  • Offices.
  • Military sites.
  • Retail.
  • Stadia.
  • Museums and galleries.
  • Prisons.
  • Train stations.
  • Airports.
  • Warehouses.
  • Factories.
  • Nurseries.
  • Shopping centres.
  • Restaurants.

Description

The Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier is an electrically operated, gravity fail-safe fire and smoke control system developed specifically to meet the life-safety requirements of BS 8524-1, with installation in accordance with BS 8524-2. The system provides 120 minutes fire integrity and up to 85 minutes radiation performance at 15 kW/m², supporting occupant tenability and protected means of escape strategies.

The barrier assembly incorporates a carbon steel barrel and integrated 24 V d.c. electric motor, with a high-performance flexible fire curtain fabric capable of withstanding temperatures in excess of 1000°C. Barrel deflection performance complies with BS 6323-5, ensuring structural stability during deployment. A two-section T-profile bottom rail delivers smooth, controlled descent and reliable gravity fail-safe operation in the event of power or system failure.

The Flameshield 8524 (S) includes internal battery back-up, enabling continued operational readiness during mains power interruption. A two-stage closing sequence with split-drop and timed delay options supports phased evacuation and enhanced safety management in occupied buildings.

Designed to support architectural intent as well as performance, the system can be concealed above ceiling lines, with end plates, guides and head boxes available in specialist RAL finishes, allowing seamless integration with interior design schemes.

A comprehensive range of ancillary safety equipment is available, including egress switches, access switches, obstruction detection, and heat and smoke activation, all fully tested to Annex H of BS 8524-1. Optional audible and visual warning systems, including voice warning devices, can be specified to enhance occupant awareness during curtain deployment.

The Flameshield 8524 (S) is fully compliance-tested, offers low maintenance requirements, and is capable of full reset following fire testing without the need for specialist engineer attendance.

Independent testing and approval has been carried out by Warrington Fire Research Centre and Exova, including:

  • BS EN 1634-1 – fire resistance and radiation performance
  • BS EN 1634-3 – smoke containment
  • BS 8524-1 – active fire curtain barrier assemblies

Associated Warrington test references include WF 341175 (deflection), WF 347098 (smoke), WF 399170 (motor performance) and WF 399421 (surface spread of flame to BS 476-6 and BS 476-7).

Features and benefits:

  • Gravity fail safe closes without mains power.
  • Internal battery back up.
  • Provides smoke control.
  • Lightweight slimline compact design.
  • Two stage closing operation. Split drop and delay drop.
  • Compliance tested to maintain building fire safety and integrity in accordance with BS 8524-1.
  • Installed in accordance with BS 8524-2.
  • Can be hidden neatly above the ceiling line to assist the building design and aesthetics.
  • Voice warning devices available.
  • Fully resets after fire test without the need for engineers to attend.
  • Low maintenance costs.
  • Timed delay closing.

General information

Color

Other

Manufacturer guidance

All RAL colours available.

Finish

Powder-coated

Guidance for specification option:

Powder coated to C3 class. Additional corrosivity classes available to C3H through treatment and application of specialist primer.

Material

Carbon steel

Shape

Rectangle

Length

Bespoke

Width

10000 mm

Height

10000 mm

Guidance for specification option:

Overall width and height restrictions may apply.

Warranty description

One year

Guidance for specification option:

Extended warranty available on application.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

SKU Code

FS 8524S

Specification data - Vertical active fire curtain barriers

Classification data

Standards

-

Barrier assemblies

To BS 8524-1, BS EN 1634-1 and BS 1634-3.

Test standards

Vertical, horizontal and angled to BS EN 1634-1.

Third-party certification

IFCC 1542 and IFCC 3425. Warrington Fire Report 340986.

Size

-

Manufacturer guidance

Maximum size (w x h): 5000 x 6000 mm. (32 m²). Insert requirements.

Performance

-

Pressure and impact

Tested to BS 5234-1 (Clause 5.2 BS 8524-1) Warrington Test number WIL 403113 Issue 3.

Durability class

C1.

Smoke containment

No smoke seals.

Fire resistance

120 minutes integrity classified to EW60.

Manufacturer guidance

To BS 476-6 and BS 476-7.

Reaction to fire

To BS 476-6 and BS 476-7.

Deployment

Immediate deployment from receipt of alarm signal. Split and delay drop facilities with timed hold.

Activation

Specialist panel with internal battery back up and modified motor. Activation on receipt of relevant alarm signal.

Accessories

Partial Drop.

Guidance for specification option:

The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes

Emergency Retract.

Guidance for specification option:

The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available.

BMS Interface.

Guidance for specification option:

The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed.

Single Photo Cell.

Guidance for specification option:

Tested and Passed by Exova to BS 8524-1 Annex H

Audio / Visual / Spoken Warning Unit.

Guidance for specification option:

The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An Audio / Visual / Spoken warning unit can be interfaced with this using power supplied by the primary / secondary source or via an external source.

Egress switches.
Access switches.

Radiation

85 minutes at 15 kW/m².

Fabric

Fire rated fabric 0.54 mm thick stainless steel wire reinforced, aluminium pigmented and fire retardant polymer.

Guidance for specification option:

  • Independently tested for fire propagation to BS 476-6, BS 476-7 which relates to surface spread of flame and in accordance with approved document B 2006.
  • As a requirement of BS EN 1634-1, the fabric and curtain are tested as a complete assembly in compliance with BS EN 1363-1 and BS EN 1363-2.

Barrel

Carbon steel tube.

Guidance for specification option:

Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.

Colour and finish

-

Manufacturer guidance

Consult manufacturer and insert requirements. Available in any RAL colour.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Manufacturing plant location

Material

Carbon steel

Expected Life

Ten year

Guidance for specification option:

Lifetime under BS 8524-2.

Manufacturer guidance

Lifetime under BS 8524-2.

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Product certifications

Certifire Certificate

Certifire Certificate

3rd Party Manufacture Fire Curtains to BS EN 1634-1

IFCC

IFCC

Fire and Smoke Curtain Installation and Servicing third party to BS 8524-2

IFCC

IFCC

Fire and Smoke Curtain Manufacture third party to BS 8524-1

smas WORKSAFE

smas WORKSAFE

SMAS 2025 (SSIP)

Literature

A1S Group Specification Sheet: Flameshield 8524 S

A1S Group Specification Sheet: Flameshield 8524 S

A1S Group Drawing (Face Fit) Flameshield 8524 S

A1S Group Drawing (Face Fit) Flameshield 8524 S

A1S Group Drawing (Reveal Fit) Flameshield 8524 S

A1S Group Drawing (Reveal Fit) Flameshield 8524 S

CPD materials

The Functionality, Design and Compliance of Fire and Smoke Curtains​

The Functionality, Design and Compliance of Fire and Smoke Curtains​

Case studies

Fire Curtains to EW120 for 125 Deansgate Manchester UK

Fire Curtains to EW120 for 125 Deansgate Manchester UK

Similar products from A1S Group

Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain

Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain

Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Fire and Smoke Curtain

Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Fire and Smoke Curtain

Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain

Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain