Vertical active fire curtain barrier providing 120 minutes integrity and up to 85 minutes radiation performance, tested to BS 8524-1 and installed to BS 8524-2.
Vertical active fire curtain barrier suitable for applications requiring BS 8524-compliant fire compartmentation and life-safety performance, including protected means of escape, atria, lobbies, reception areas, corridor separation, openings in fire-resisting walls, boundary protection, escalators, stairwells, lift shafts and lift lobbies.
Regularly specified within hospitals and healthcare facilities, schools and universities, hotels, high-rise and mixed-use developments, offices, retail environments, stadia, museums and galleries, as well as transport infrastructure such as train stations and airports. Also suitable for warehouses, factories, nurseries, shopping centres, restaurants, and defence or custodial environments where certified fire containment is critical.
The Flameshield 8524 Fire curtain is designed for multiple applications such as:
The Flameshield 8524 Vertical Active Fire Curtain Barrier is an electrically operated, gravity fail-safe fire curtain system developed to meet the life-safety requirements of BS 8524-1, with installation in accordance with BS 8524-2. The system provides 120 minutes fire integrity and up to 85 minutes radiation performance at 15 kW/m², supporting occupant tenability and protected means of escape strategies within a wide range of building types.
The barrier assembly comprises a carbon steel barrel and integrated 24 V d.c. electric motor, incorporating a high-performance flexible fire curtain fabric capable of withstanding temperatures in excess of 1000°C. Barrel deflection performance complies with BS 6323-5, ensuring stability and controlled deployment. A two-section T-profile bottom rail delivers smooth descent, consistent tension and reliable gravity fail-safe operation in the event of power or system failure.
The system incorporates internal battery back-up, ensuring continued operational readiness during mains power interruption. A two-stage closing sequence, with split-drop and timed delay options, supports phased evacuation and effective fire strategy implementation in occupied buildings.
Designed to support architectural integration, the Flameshield 8524 can be concealed above ceiling lines, minimising visual impact while maintaining certified fire performance.
A comprehensive range of ancillary safety devices is available, including egress switches, access switches, obstruction detection, and heat and smoke activation, all fully tested in accordance with Annex H of BS 8524-1. Optional audible and visual warning systems, including voice warning devices, can be specified to enhance occupant awareness during deployment.
The Flameshield 8524 is fully compliance-tested, offers low maintenance requirements, and is capable of full reset following fire testing without the need for specialist engineer attendance.
Independent testing and approval has been carried out by Warrington Fire Research Centre and Exova, including fire, radiation and smoke containment testing to BS EN 1634-1 and BS EN 1634-3, in accordance with BS 8524-1. Associated Warrington test references include WF 341175 (deflection), WF 347098 (smoke), WF 399170 (motor performance) and WF 399421 (surface spread of flame to BS 476-6 and BS 476-7).
Features and benefits:
Color | Beige Black Blue Bronze Brown |
Finish | Powder-coated |
Material | Carbon steel Fabric Guidance for specification option: Steel and aluminium fabric. Polymer Steel |
Shape | Rectangle |
Length | Bespoke |
Width | 5000 mm Guidance for specification option: Overall width and height restrictions may apply. |
Height | 6000 mm Guidance for specification option: Overall width and height restrictions may apply. |
Warranty description | One year Guidance for specification option: Extended warranty available on application. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
SKU Code | FS 8524 |
Classification data | |
Standards | |
Barrier assemblies | To BS 8524-1, BS EN 1634-1 and BS 1634-3. |
Test standards | Vertical, horizontal and angled to BS EN 1634-1. |
Third-party certification | IFCC 1542 and IFCC 3425. Warrington Fire Report 340986. |
Size | Guidance for specification option: Maximum size (width x height): 5000 x 6000 mm. (32 m²). Insert requirements. |
Performance | |
Pressure and impact | Tested to BS 5234-1 (Clause 5.2 BS 8524-1) Warrington Test number WIL 403113 Issue 3. |
Durability class | C1. |
Smoke containment | No smoke seals. |
Fire resistance | 120 minutes integrity classified to EW 60. |
Reaction to fire | To BS EN 13501-1, s1. |
Barrier units | Single. |
Deployment | Full. Guidance for specification option: As standard. Immediate deployment from receipt of alarm signal. Split and delay drop facilities with timed hold. Multipositional. Guidance for specification option: Optional: Partial drop. The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes. |
Activation | Specialist panel with internal battery back up and modified motor. Activation on receipt of relevant alarm signal. |
Accessories | Emergency retract. BMS Interface. Single phot cell. Audio/ visual/ spoken warning unit. Egress switches. Access switches. |
Fabric | Fire rated fabric 0.54 mm thick stainless steel wire reinforced, aluminium pigmented and fire retardant polymer. Guidance for specification option:
|
Barrel | Carbon steel tube. Guidance for specification option: Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards. |
Colour and finish | Guidance for specification option: Consult manufacturer and insert requirements. Available in any RAL colour. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Manufacturing plant location | |
Material | Carbon steel Fabric Guidance for specification option: Steel and aluminium fabric. Polymer Steel |
Expected Life | Ten year Guidance for specification option: Lifetime under BS 8524-2. Manufacturer guidanceLifetime under BS 8524-2. |
This BIM object has been authored to meet the requirements of the
Find out more about the
| Platform | Compatible | Version |
|---|---|---|
| - | 1 | |
| - | 1 |
Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire and Smoke Curtain
Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested
Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain
Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Fire and Smoke Curtain
Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested
Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain
Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain