Vertical active fire and smoke curtain barrier providing up to 120 minutes integrity and EW120 radiation control, achieving 10.7 kW/m² at 120 minutes, tested to BS 8524-1 and installed to BS 8524-2.

Jump to:
BOS
+44 (0)1204 383839 Website

Application

Vertical active fire and smoke curtain barrier designed for large internal openings requiring robust fire compartmentation and smoke control. Suitable for protected means of escape, atria, lobbies, reception areas, corridor separation, openings in fire-resisting walls, boundary protection, escalators, stairwells, lift shafts and lift lobbies.

Commonly specified within hospitals and healthcare facilities, schools and universities, hotels, high-rise buildings, mixed-use developments, commercial offices, retail environments, stadia, museums and galleries, as well as transport infrastructure, industrial and utility installations. Also appropriate for defence, custodial, policing and secure environments where large-span fire and smoke containment is required without compromising architectural intent.

Description

The Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier is an electrically operated, gravity fail-safe fire and smoke control system engineered for large opening applications, delivering up to 120 minutes fire integrity and EW120 radiation performance. Radiation levels remain below 15 kW/m², achieving 10.7 kW/m² at 120 minutes, supporting tenability requirements and protected escape routes within complex building layouts.

The barrier assembly incorporates a carbon steel barrel and integrated 24 V d.c. electric motor, with a high-performance flexible fire curtain fabric capable of withstanding temperatures in excess of 1000°C. Designed specifically to accommodate larger spans, the EW120 Max/S is available in standard sizes up to 10,000 mm wide by 4,000 mm high, while maintaining barrel deflection compliance with BS 6323-5. A two-section bottom rail ensures controlled descent, stability and reliable gravity fail-safe deployment in the event of power or system failure.

The Flameshield EW120 Max/S offers enhanced architectural integration, with the ability to be concealed above ceiling lines and supplied with colour-finished end plates, guides and hoods, allowing coordination with interior finishes without compromising fire performance.

A two-stage closing operation, timed delay options and a comprehensive range of fully tested ancillary safety devices - including egress switches, access switches, obstruction detection, and heat and smoke activation - are incorporated and tested in accordance with Annex H of BS 8524-1. Optional audible and visual warning systems, including voice warning devices, can be specified to support occupant awareness during deployment.

The system is fully compliance-tested, offers low maintenance requirements, and is capable of full reset following fire testing without the need for specialist engineer intervention. Manufacture and construction align with tested assemblies and relevant sections of BS EN 16034, ensuring consistency, reliability and regulatory confidence.

Independent fire, radiation and smoke containment testing has been carried out and approved by Warrington Fire Research Centre and Exova, in accordance with BS 8524-1, BS EN 1634-1 (fire resistance and radiation performance) and BS EN 1634-3 (smoke containment).

Features and benefits:

  • Gravity fail safe closes without mains power.
  • Provides smoke control.
  • Lightweight slimline compact design.
  • Two stage closing operation.
  • Compliance tested to maintain building fire safety and integrity in accordance with BS 8524-1 and installed in accordance with BS 8524-2.
  • Can be hidden neatly above the ceiling line to assist the building design and aesthetics.
  • Voice warning devices available.
  • Fully resets after fire test without the need for engineers to attend.
  • Low maintenance costs.
  • Timed delay closing.

Radiation:

  • 120 Minutes < 15 kW/m².
  • 15 Minutes - 2.617 kW/m².
  • 30 Minutes - 3.748 kW/m².
  • 60 Minutes - 6.306 kW/m².
  • 90 Minutes - 8.328 kW/m².
  • 120 Minutes -10.708 kW/m².

General information

Color

Beige

Black

Blue

Bronze

Brown

Show more

Finish

Powder-coated

Mill

Material

Carbon steel

Stainless steel

Guidance for specification option:

Stainless steel wire and reinforced glass fabric.

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

Extended warranty available on application.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

SKU Code

FS EW120 MaxS

Specification data - Vertical active fire curtain barriers

Classification data

Standards

-

Barrier assemblies

To BS 8524-1.

Test standards

Vertical, horizontal and angled to BS EN 1634-1.

Third-party certification

Warrington Fire Report 406515.

Size

Guidance for specification option:

Maximum size (width x height): 10 000 x 4000 mm. Insert requirements.

Performance

-

Smoke containment

With smoke seals.

Fire resistance

120 minutes.

Barrier units

Single.

Deployment

Full.

Guidance for specification option:

As standard.

Multipositional.

Guidance for specification option:

Optional.

The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes.

Accessories

Emergency retract.

Guidance for specification option:

The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available.

BMS interface.

Guidance for specification option:

The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed.

Single photo cell.

Guidance for specification option:

Tested and Passed by Exova to BS 8524-1 Annex H.

Audio/ visual/ spoken warning unit.

Guidance for specification option:

The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An audio/ visual/ spoken warning unit can be interfaced with this using power supplied by the primary/ secondary source or via an external source.

Multi-beam detection.

Guidance for specification option:

A multi-beam detection system is required when the barrier assembly is intended to protect a means of escape route. For more information, see BS 8524 - 2.5.8.5.2.

Fabric

4415-2-B1 fabric.

Guidance for specification option:

  • Stainless steel wire, reinforced glass fabric with a specially formulated intumescent fire retardant silicone elastomer.
  • Does not generate toxic emissions, and has a good resistance to hydrolysis.
  • At 140°C the coating system will form an expanding intumescent char.
  • The fabric has been independently tested for fire propagation in accordance with BS 476-6 in addition to this it also conforms to BS 476-7 which relates to surface spread of flame and in accordance with approved document B 2006.
  • As a requirement of BS EN 1634-1, the fabric and curtain are tested as a complete assembly in compliance with BS EN 1363-1 and BS EN 1363-2.

Barrel

Carbon steel tube.

Guidance for specification option:

Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.

Finishes

Powder-coated.
Mill.

Guidance for specification option:

C3 corrosion class available as standard. Advanced durability to corrosion class C3h on application.

Colour

Guidance for specification option:

Consult manufacturer and insert requirements. Full selection of RAL colours available.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Manufacturing plant location

Material

Carbon steel
Stainless steel

Guidance for specification option:

Stainless steel wire and reinforced glass fabric.

Expected Life

Ten year

Guidance for specification option:

Lifetime under BS 8524-2.

Manufacturer guidance

Lifetime under BS 8524-2.

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Literature

A1S Group Specification Sheet: Flameshield EW120 Max/S

A1S Group Specification Sheet: Flameshield EW120 Max/S

A1S Group Drawing (Face Fit) Flameshield EW120 Max/S

A1S Group Drawing (Face Fit) Flameshield EW120 Max/S

A1S Group Drawing (Reveal Fit) Flameshield EW120 Max/S

A1S Group Drawing (Reveal Fit) Flameshield EW120 Max/S

CPD materials

The Functionality, Design and Compliance of Fire and Smoke Curtains​

The Functionality, Design and Compliance of Fire and Smoke Curtains​

Case studies

Fire Curtains to EW120 for 125 Deansgate Manchester UK

Fire Curtains to EW120 for 125 Deansgate Manchester UK

Flameshield Fire Curtain with EW120 enhanced radiation control

Flameshield Fire Curtain with EW120 enhanced radiation control

Similar products from A1S Group

Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire and Smoke Curtain

Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire and Smoke Curtain

Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain

Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain

Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested

Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Fire and Smoke Curtain

Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Fire and Smoke Curtain

Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain

Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Fire Curtain