Two-hour fire-resisting roller shutter - E120.

Jump to:
BOS
+44 (0)1204 871001 Website

Application

Warehouses, Factories, Shopping Centres, Malls, Car Parks Department Stores.

Retail outlets, Church halls.


Performance Characteristics:

Resistance to Fire:      E120

Including Rigid Structures

E60 for Flexible Structures

Durability:                      C2 (10,000 Cycles)

 

Fire: Tested to EN1634-1 all in accordance with

EN13501- 2:2016, EN13241:2003 + A2:2016, EN16034:2014

EN15269-10.

Durability: Tested to EN15269-10 Clause J.1.2.

 

Key Attributes:

120 minute fire rating.

CE Marked fire shutter.

Approved for rigid and flexible structures (up to E60).

Industrial applications.

Multifunction as a security shutter.

 


Description

Bolton Gate Company offers probably the most comprehensive range of modern fire resisting shutters available on the market today.

 

The Fireroll E120 two-hour fire rated shutter is designed to provide fire compartmentation with security, durability and reliability in mind. This fire shutter will satisfy the needs of large or complex packages as well as meeting the most stringent safety and insurance requirements.

 

All Bolton Gate fire doors and shutters are tested and assessed by officially recognised and competent authorities.

 

Operation

Suitable for all sizes of shutters, the Speedsafe drive unit has a 230-volt nominal single phase or 400-volt nominal three phase geared induction motor with an electromagnetic brake, limit switches, release unit, a built-in starter panel and low-level push button station with emergency stop button.

 

In a fire condition, gravity failsafe closing is activated by a 24-volt DC signal (0.37 amps) from the client’s fire alarm panel to the auto reset solenoid which releases the motor brake and is backed up by a fusible link.

 

A safety brake is supplied to comply with the safeguarding requirements of EN 12604.

 

Manual operation in the event of a power loss is achieved by releasing a pull cord to close the shutter under controlled descent and a hand chain to open.

 

Curtain

Shutter curtain is constructed from continuously interlocked 76mm curved section steel laths which are securely held in place by end locks. Lath thicknesses vary dependent upon opening size.

 

Bottom Rail

Bottom rails are galvanised, and roll formed into a Tee section.

 

Side Guides

Channel section galvanised mild steel guides with slotted fixings for expansion in a fire are fixed to the jambs with continuous steel angles.

 

Roller

The roller is made from seamless tube of sufficient diameter and wall thickness to resist deflection and is supported in bearings mounted on each endplate.

 

Endplates

Fabricated from steel plate and prepared to accept the coil casing. Securely bolted to steel fixing angles which are drilled for attachment to the structure at the correct centres.

 

Coil Casing

A galvanised steel coil casing is supplied to maintain the fire seal at the head.

 

Finish

Fireroll E120 is supplied in a galvanised finish as standard. Where non-galvanised parts are utilised, these are finished with one coat of primer paint.

 

Maximum Sizes

7000mm wide x 7000mm high as standard

12000mm wide - height dependent (please contact our sales team to discuss)

 

Weight

Varies with opening size dependent on lath/barrel/casing requirements but approximately 50kgs/m².

 

Options

· Heat/smoke detectors

· Audio visual warning

· Polyester powder coated finish to a range of standard RAL colours.

· Grade 304 or 316 stainless steel.

· Obstruction detection (light curtain or safety photocell).

 


General information

Color

-

Manufacturer guidance

Galvanized as standard, can get Powder coated RAL.

Finish

Galvanized

Powder-coated

Other

Material

Carbon steel

Steel

Stainless steel

Shape

Square

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Material

Carbon steel

Steel

Stainless steel

Uniclass

Pr_30_59_84_30 Fire-resisting roller shuttersPrimary
Pr_30_59_84_73 Roller shutters

CAWS

L20/60 Doors

L20/530 Sliding folding external doors

L20/610 Roller shutters/ curtains

Product range

Fire

Specification data - Fire-resisting roller shutters

Standard

Internal / external fire rated roller shutter CE marked to BS EN 13241 and BS EN 16034.

Opening sizes

Guidance for specification option:

Maximum of 7000 mm clear width x 7000 mm clear height as standard; Maximum approved capability is 12000 mm clear width x height dependent - please contact our Sales Team for further information.

Format

Internal/ external.

Arrangement

Vertical.

Performance

-

Fire performance

-

Resistance to fire

Integrity (E) 120.

Guidance for specification option:

E120 in accordance with EN 13501-2.

Resistance to wind load

Class 3.

Frame and guides

-

Material

Steel.

Finish

Galvanized.

Guidance for specification option:

Standard.

Powder coated.

Guidance for specification option:

Insert colour requirements below.

Colour

Silver.

Guidance for specification option:

Standard (galvanized finish).

RAL.

Guidance for specification option:

Insert colour requirements (powder-coated finish only).

Shutter curtain.

-

Lath material

Galvanized steel.

Guidance for specification option:

As standard.

Stainless steel, 1.4301 (304) grade.

Guidance for specification option:

Optional.

Stainless steel, 1.4401 (316) grade.

Guidance for specification option:

Optional.

Profile

Curved.

Finish and colour

Galvanized.

Guidance for specification option:

Standard.

Powder coated, RAL.

Guidance for specification option:

Insert colour requirements.

Stainless steel.

Execution

Workmanship in joinery.

Operating forces

Electric operation as standard complete with manual override for use in the event of power failure.

Mode

Activation via a signal for the fire alarm system to an auto reset solenoid.

Guidance for specification option:

When activated, releases the motor brake allowing the shutter to  close by gravity with a controlled descent.

Operation

230 V nominal, single-phase.

400 V nominal, three-phase.

Manufacturer guidance

Speedsafe motor mounted on one end plate. Standard operation is via a low-level push button station with emergency stop button. A pull cord and hand chain are provided for use in the event of power failure.

Accessories

Not required.

Fire door control panel with integrated audio-visual warning.

Heat/ smoke detectors.

Weight

50 kg/m².

Guidance for specification option:

Varies with opening size but approximate.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Carbon steel

Steel

Stainless steel

Manufacturing plant location

Recyclability

95%

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Expected Life

20 year

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

Constructionline

Constructionline

Constructionline Gold

ISO 9001 Quality Management

ISO 9001 Quality Management

Certificate of Management System Registration - ISO 9001:2015

dhf certificate

dhf certificate

DHF Membership

Literature

Fire Shutter - Fireroll E120 - Two Hour Fire Resisting Roller Shutter

Fire Shutter - Fireroll E120 - Two Hour Fire Resisting Roller Shutter

Similar products from Bolton Gate Company

Acoustic Roller Shutter - Sonaroll

Acoustic Roller Shutter - Sonaroll

Fire Shutter - Fireroll Acoustic

Fire Shutter - Fireroll Acoustic

Fire Shutter - Fireroll E30

Fire Shutter - Fireroll E30

Fire Shutter - Fireroll E60

Fire Shutter - Fireroll E60

Fire Shutter - Fireroll EW

Fire Shutter - Fireroll EW

Fire Shutter - Fireroll VR60

Fire Shutter - Fireroll VR60

Fire Shutter - Horizontal

Fire Shutter - Horizontal

Insulated Roller Shutter

Insulated Roller Shutter

SecRoll SR1, SR2 & SR3 Security Shutters

SecRoll SR1, SR2 & SR3 Security Shutters

Security Roller Shutter

Security Roller Shutter