FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

Verified by manufacturer 11 days ago

Design .01 - Manual control and thermal

Mandik UK Limited Variant:
Third party certifications:
  • DoP

    DoP

    Certificate type

  • Certificate of constancy of performance

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

  • EPD

    EPD

    Certificate type

A manual or motorised fire damper for air conditioning ducts.

Jump to:
0117 4526376 Website

Application

The fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire-separating constructions. The fire damper can be installed into:

  • Solid wall construction, e.g. made of normal concrete/ masonry or porous concrete with a minimum thickness of 100 mm.
  • Gypsum wall construction with a minimum thickness of 100 mm.
  • Solid ceiling construction, e.g. made of normal or porous concrete, with minimum thickness according to BS EN 1366-2.

Additional applications may be available, please reference product Technical Specifications for more detail.

Description

A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors.

Features and benefits:

  • Dampers from 150 x 150 mm to 1500 x 800 mm.
  • Certified to BS EN 15650.
  • Tested in accordance with BS EN 1366-2.
  • Classified to BS EN 13501-3+A1.
  • Fire resistance EI 120 S - 500 Pa.
  • Damper actuating mechanical or electrical.

General information

Color

Silver

Finish

Galvanized

Material

Steel

Calcium silicate

Shape

Rectangle

Square

Length

375 mm

Width

150 mm

180 mm

200 mm

225 mm

250 mm

Show more

Height

150 mm

180 mm

200 mm

225 mm

250 mm

Show more

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To BS EN 15650.

Test

To BS EN 1366-2.

Classification

To BS EN 13501-3.

Aerodynamic performance

To BS EN 1751.

Guidance for specification option:

Damper body: Class C (minimum); Damper blade: Class 2 (minimum).

Arrangement

Single-blade.

Classification

EIS120.

Manufacturer guidance

Refer to the manufacturer's literature for placement and installation details to achieve the required fire resistance value.

Material

Zinc-coated steel.

Fusible links

-

Fusing temperature

72°C.

Guidance for specification option:

As standard.

104°C.

147°C.

Spare fusible links

-

Manufacturer guidance

Insert requirements or omit.

Dimensions

-

Manufacturer guidance

Consult manufacturer's literature for performance details and insert requirements.

  • Damper body: From 150 x 150 mm to 1500 x 800 mm.
  • The dampers are available in any 5 mm increment within their minimum and maximum sizes.
  • Construction length: 375 mm.

Actuator

Mandik.

Control module

Not required.

Communication and control module MDCM.

Guidance for specification option:

The MDCM damper control module is connected on a bi-directional communication loop back to a control panel, typically located at the FCC. This accessory is only required with MANDIK control systems.

Cladding

Not required.

Protective cladding boards.

Guidance for specification option:

Protective cladding boards must be used as a part of

installation with weichschott system.

Frame

Not required.

Reinforcing frame VRM-Q.

Guidance for specification option:

If the damper is installed outside the fire separation construction, a damper side A ≥ 800 mm and fire resistance is EI 90 S, VRM-Q reinforcement frame must be

used.

Duct connection

Mandik FFDM breakaway joint.

Guidance for specification option:

FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained.

Refer to FFDM – Technical specifications for options and insert requirements.

Breakaway joint (supplied by others).

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Breakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper.

Sustainability data

Country of product manufacture

Czechia

Material

Steel

Calcium silicate

Third party certifications

Third party certifications

DoP

DoP

FDMQ 120 – Declaration of performance (CE)

DoP

DoP

FDMQ 120 – Declaration of performance (UKCA)

Certificate of constancy of performance

Certificate of constancy of performance

FDMQ 120 – Certificate (CE)

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

FDMQ 120 – Certificate (UKCA)

EPD

EPD

Environmental Product Declaration - Fire Dampers

Literature

FDMQ 120 – Technical specifications (166/22)

FDMQ 120 – Technical specifications (166/22)

FDMQ 120 – Solid Wall Gypsum - CID (UKCA)

FDMQ 120 – Solid Wall Gypsum - CID (UKCA)

FDMQ 120 – Solid Wall Firebatt - CID (UKCA)

FDMQ 120 – Solid Wall Firebatt - CID (UKCA)

FDMQ 120 – Solid Wall 2 Damper Battery - CID (UKCA)

FDMQ 120 – Solid Wall 2 Damper Battery - CID (UKCA)

FDMQ 120 – Solid Wall 4 Damper Battery - CID (UKCA)

FDMQ 120 – Solid Wall 4 Damper Battery - CID (UKCA)

FDMQ 120 – Lightweight Wall Gypsum - CID (UKCA)

FDMQ 120 – Lightweight Wall Gypsum - CID (UKCA)

FDMQ 120 – Lightweight Wall FireBatt - CID (UKCA)

FDMQ 120 – Lightweight Wall FireBatt - CID (UKCA)

FDMQ 120 – Slab Firepro - CID (UKCA)

FDMQ 120 – Slab Firepro - CID (UKCA)

FDMQ 120 – British Gypsum Shaftwall - CID (UKCA)

FDMQ 120 – British Gypsum Shaftwall - CID (UKCA)

FFDM – Technical specifications (137/19)

FFDM – Technical specifications (137/19)

Similar products from Mandik UK Limited

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised  - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm)  - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper