FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

Verified by manufacturer 15 days ago

Design .01 Manual and thermal

Mandik UK Limited Variant:
Third party certifications:
  • Hygiene requirements to VDI 6022

    Certificate type

  • DoP

    DoP

    Certificate type

  • Certificate of constancy of performance

    Certificate type

  • Type Examination Certificate

    Certificate type

  • EPD

    EPD

    Certificate type

A single blade fire damper for HVAC ductwork.

Jump to:
0117 4526376 Website

Application

Fire dampers are suitable for installation in arbitrary positions in vertical and horizontal passages of fire-separating constructions. The fire damper can be installed into:

  • Solid wall construction made of, e.g. normal concrete/ masonry, porous concrete with a minimum thickness 100 mm.
  • Solid ceiling construction made of, e.g. normal concrete with a minimum thickness of 110 mm or porous concrete with a minimum thickness 125 mm.
  • Gypsum wall construction with fire classification EI 120 or EI 90.
  • Outside of wall construction (sold and flexible).

Additional applications may be available, please reference product Technical Specifications for more detail.

Description

A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors.

Features and benefits:

  • Dampers from 180 x 180 mm to 1600 x 1000 mm.
  • CE certified to EN 15650.
  • Tested in accordance with EN 1366-2.
  • Classified to EN 13501-3+A1.
  • Fire resistance up to EI 120 S.
  • Damper actuating mechanical or electrical.
  • Can be used in explosion-hazard environments.

General information

Color

Silver

Finish

Galvanized

Material

Steel

Calcium silicate

Shape

Rectangle

Square

Length

375 mm

Width

180 mm

200 mm

225 mm

250 mm

280 mm

Show more

Height

180 mm

200 mm

225 mm

250 mm

280 mm

Show more

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To EN 15650.

Test

To EN 1366-2.

Classification

To EN 13501-3.

Aerodynamic performance

To EN 1751.

Guidance for specification option:

Damper body: Class C; Damper blade: Class 2.

Arrangement

Single-blade.

Classification

EIS90.

EIS120.

Manufacturer guidance

Refer to the manufacturer's literature for placement and installation details to achieve the required fire resistance values.

Material

Zinc-coated steel.

Fusible links

-

Fusing temperature

72°C.

Guidance for specification option:

As standard.

104°C.

147°C.

Spare fusible links

-

Manufacturer guidance

Insert requirements or omit.

Dimensions

-

Manufacturer guidance

Consult manufacturer's literature for performance details and insert requirements.

  • Damper body: From 180 x 180 mm to 1600 x 1000 mm.
  • The dampers are available in any 5 mm increment within their minimum and maximum sizes.
  • Construction length: 375 mm.

Duct connection

Mandik FFDM breakaway joint.

Guidance for specification option:

FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained.

Refer to FFDM – Technical specifications for options and insert requirements.

Breakaway joint (supplied by others).

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Breakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper.

Sustainability data

Material

Steel

Calcium silicate

Third party certifications

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

Hygiene requirements to VDI 6022

Hygiene requirements to VDI 6022

Hygienic assessment - Fire dampers

DoP

DoP

FDMA – Declaration of performance

Certificate of constancy of performance

Certificate of constancy of performance

FDMA – Certificate

Type Examination Certificate

Type Examination Certificate

FDMA – Certificate ATEX

EPD

EPD

Environmental Product Declaration - Fire Dampers

Literature

FDMA – Technical specifications (018/01)

FDMA – Technical specifications (018/01)

FFDM – Technical specifications (137/19)

FFDM – Technical specifications (137/19)

Similar products from Mandik UK Limited

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised  - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm)  - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper