NBS Source
I'm a manufacturer
Compare variants

SmokeMaster SM-ST

Verified by manufacturer 8 days ago

D120

Colt International Ltd Variant:

Fixed smoke curtain for limiting or channelling combustion gases in the event of a fire. The curtain forms permanent barriers and thus prevents the spread and cooling of smoke gases.

Jump to:
+44 (0)23 9245 1111 Website

Application

Provision of smoke and heat protection for most kinds of industrial and commercial buildings.

Description

SmokeMaster SM-ST curtains consist of adjacent smoke curtains fixed together with a clamping profile. The fabric is mechanically fixed to the profiles and kept taut with a weight at the bottom.

SmokeMaster SM-ST curtains are commonly used in high industrial buildings where a permanent barrier is not inconvenient and does not interfere with production processes. They can also be used in other building types and fixed within the roof area due to its low weight.

Product Highlights:

  • SmokeMaster SM-ST curtains have been tested and certified according to EN 12101-1:2005+A1:2006 and is CE marked.
  • Low weight and therefore easy to attach to the building structure.
  • Pre-fabricated assembly delivered with a modular design.
  • Unit length: 1.0 m to an infinite length. 
  • Unit height: 0.5 m to 15 m. 

Product Technical Information:

Versions:

The compact and lightweight SmokeMaster SM-ST can be installed into many different kinds of roofs and shapes. Due to its low weight it places an insignificant load onto the building.

The ducting of building services cables through the smoke curtain is possible without any problems. Residual openings are closed off to maintain temperature resistance, for example by means of galvanised steel sleeves for round ducting or galvanised steel angle profiles for straight ducting.

Classifications:

In accordance with EN 12101-1: Temperature / time classification: D120 / DH60 / DH120.

General information

Material

Glass Fibre

Shape

Rectangle

Uniclass

Pr_25_80_79_86 Static smoke barriersPrimary

Product range

Smoke & Fire Curtains

Specification data - Static smoke barriers

Classification data

Standard

To BS EN 12101-1.

Third-party certification

EU certificate 0672-CPD-0146. General building approval (AbZ) no. 56-4211-949.

Classification categories

-

Standard temperature

D 120.

Guidance for specification option:

Tested at 600°C for120 minutes.

Fabric class is A2-s1, d0 according to EN 13501-1.

Form

Flexible, 455 g/m².

Guidance for specification option:

The fabric comprises a satin weave fibreglass fabric with a silver polyurethane coating on both sides providing an excellent reflection of

heat.

Dimensions

-

Manufacturer guidance

Insert requirements.

  • Maximum overall length: 150 m.