NBS Source
I'm a manufacturer
Compare variants

Raised Access Floor Fire Barrier - Cavity barrier

Verified by manufacturer 2 months ago

One Hour RAF Barrier

AIM Variant:

A cavity barrier for below raised access flooring systems.

Jump to:
+44 (0)1293 582400 Website

Application

Raised Access Floor Barriers are required for four applications:

  • Subdivision of large uninterrupted cavities.
  • Alignment under a partition, to maintain partition rating.
  • Reduce flanking transmission of sound.
  • Help create a plenum chamber under a raised access floor system.

Description

AIM Raised Access Floor Barrier prevents the passage of flame and smoke through the under floor cavity, for at least the period of fire rating specified. AIM Raised Access Floor Barrier is made from high density Rockwool stone wool slab, faced with Class 0 impervious foil facing on both sides. It is available cut to size or in slabs suitable for cutting on site.


Features and benefits:

  • High density foil faced stone wool barrier.
  • For use within voids up to 400 mm.
  • Reduces airborne transmission of sound by a minimum of 21 db RW.
  • Solutions for power and communication cables.
  • Length: 1000 mm.
  • Widths: 75 mm, 100 mm and 125 mm (depending on the fire rating required).
  • Voids: 50–400 mm (barrier to be compressed by 5%).
  • Available as ½ hour, 1 hour, and 2 hour raised access floor fire barrier (dependent on thickness).
  • Available cut to size and supplied with the required fixing clips.
  • Available in slab form for cutting on site as required.
  • Foil faced available. Also available polythene sleeved.
  • The product is installed with three ‘L’ clips per length of barrier.
  • Minor construction imperfections should be sealed with a fire rated intumescent mastic.
  • Prevents the passage of fire and smoke through underfloor cavities.
  • Reduces airborne sound through underfloor voids.
  • The product provides up to 120 minutes integrity and insulation when tested to BS EN 13664.
  • Allows for power and communications to be run below the barrier.
  • When tested in-conjunction with a carpeted Kingspan Raised Access Floor system, the room to room sound reduction was at least 52 dBnfw through the path of the fire barrier. This result was achieved with all fire solutions. 

General information

Color

Other

Guidance for specification option:

Foil faced with AIM Logo.

Finish

Foil

Guidance for specification option:

Aluminum foil printed with company logo.

Material

Stone wool

Guidance for specification option:

High density stone wool.

Shape

Rectangle

Length

1000 mm

Width

75 mm

100 mm

125 mm

Manufacturer guidance

Standard sizes, depending on the fire rating required.

The product is supplied in slab form or pre-cut to height oversized to allow for compression.

Height

Bespoke

Manufacturer guidance

The product is supplied in slab form or pre-cut to height oversized to allow for compression.

Uniclass

Pr_25_80_81_51 Mineral wool fire-stoppingPrimary

CAWS

K41/340 Cavity barriers

K41/340 Cavity barriers

P12/360 Mineral wool rigid batts

P12/40 Mineral wool rigid batts

Product range

Fire Barriers

Specification data - Mineral wool fire-stopping

Material

-

Facing

Foil faced.

Fire performance

Tested to BS EN 1366-4: Euroclass A1, non combustible.

Sound insulation rating

≥RW 21 dB.

Guidance for specification option:

AIM Raised Access Floor Barrier provides at least RW 21 dB sound reduction. The acoustic performance of the floor system must also be considered when assessing the room-to-room sound reduction figure.

Length

1000 mm.

Fire resistance

120 minutes integrity / 60 minutes insulation.

Thicknesses

100 mm.

Opening size

-

Manufacturer guidance

For use in cavities up to 400 mm. Insert requirements.

There are no unsupported options; barrier must be installed with fixing clips.

Environmental

Global warming potential = zero.

Guidance for specification option:

AIM fire barrier products are manufactured from stone wool insulation which is universally recognised as being a sustainable and environmentally friendly material’.

Accessories

Not required.

Acrylic fire rated intumescent mastic.

Guidance for specification option:

310 ml cartridge.

Foil tape for air tightness, 100 mm x 45 m.

Guidance for specification option:

Length: 45 m.

Widths: 100 mm, 125 mm and 150 mm.

Foil tape for air tightness, 125 mm x 45 m.

Foil tape for air tightness, 150 mm x 45 m.

Show more

ThermalConductivity

λ = 0.036 W/mK.

Literature

AIM Raised Access Floor Barrier Technical Guide 2022

AIM Raised Access Floor Barrier Technical Guide 2022

Similar products from AIM

Fire Stop Strip

Fire Stop Strip

Party Wall Fire Closers -

Party Wall Fire Closers -

Wall Cavity Barrier (Red Edition)

Wall Cavity Barrier (Red Edition)