NBS Source
I'm a manufacturer

OS Loop Control System

Verified by manufacturer 8 months ago

SE Controls

OSLoop is a modular smoke control system. It consists of a centralised coordination module (the coordinator) and between 1 and 16 remotely mounted manual control points (MCPs). Larger systems can be c

Jump to:
+44 (0)1543 443060 Website

Application

Modular smoke ventilation.

Description

The coordinator controls power and data to the networked system fully monitoring primary (mains) and secondary (battery*) power supplies. The OSLoop system intelligently monitors current requirements of the system and determines how and when the MCPs can call on this power to activate AOVs. 


Each MCP contains actuator switching circuitry which also monitors the actuator cabling and circuitry for faults. If a fault is detected, then the MCP raises a local alarm and also informs the coordinator so the remote alarms can be triggered. The MCP also provides support for up to three smoke detectors. Again this circuitry monitors the detectors and cabling checking for faults. In addition, the MCP may be configured to work independently or grouped in the same system. 


Features 

  • 40% less cable costs than a conventional system 
  • 50% less devices compared to conventional systems 
  • Reduced system installation time 
  • EN12101 Pt.10 2005 + C1: 2007 compliant 
  • EMC tested to EN61000-6-2 and EN61000-6-3 
  • LVD tested to EN60335-1 as amended by EN60335-2-103 

* Batteries Sold separately 

General information

Color

Beige

Finish

Powder-coated

Material

Steel

Shape

Rectangle

Length

305 mm

Width

121 mm

Height

381 mm

Uniclass

Pr_75_50_18_51 Mechanical services control panelsPrimary

Product range

Controls

Specification data - Mechanical services control panels

Enclosure

-

Ingress protection (minimum)

IP 20.

Colour

White.

Isolator

-

Rated operational current (In)

4 A.

Rated operational voltage (Ue)

230 V.

Rated operational frequency

50/ 60 Hz.

Rated short-time withstand current (Icw) for 1 s

Output VA: 25.5 V d.c. at 7 A continuous, 9 A for 60 seconds, Output VB: 27.6 V d.c. at 7 A continuous, 10 A for 60 seconds.

Guidance for specification option:

Operation at elevated temperatures may reduce battery life.


Cable entry

Top.

Mass

4.1 kg.

Guidance for specification option:

Approximate.

RelativeHumidity

10–90% (non-condensing).

TemperatureRange

Storage: 20–75°C, Operating: 0–40°C.

Battery back-up

2 x 12 V d.c. 12.0 Ah sealed lead-acid batteries.

Sustainability data

Country of product manufacture

United Kingdom

Literature

Understanding Smoke Ventilation Compliance

Understanding Smoke Ventilation Compliance

SE Controls Product Specification Guide

SE Controls Product Specification Guide

OSLoop Control System

OSLoop Control System