NBS Source
I'm a manufacturer

LPBS865 Open Class Symphoni Addressable Beacon Sounder IP65 Red Body White Flash VAD

Verified by manufacturer 2 months ago

ADT Fire and Security

Open class Symphoni addressable beacon sounder IP65 red body white flash VAD.

Jump to:
Website

Application

Alarm systems.

Description

The LP Symphoni range of Sounders and Sounder Beacons are designed to operate on the robust MZX digital loop,

An internal line isolator automatically provides short circuit protection against able faults thus reducing the need for

additional line isolator modules.


The addressable loop powered sounders meet the

requirements of EN 54-3 whilst the loop powered

addressable sounders with beacon are also approved to

EN 54-23 as open category devices.


A high (103 dB) output or low (90 dB) output can be

selected for any of the 16 selectable tones.


Programming has been simplified by allowing the tone,

volume and flash rate to be set by the MZX Consys

configuration utility. This means adjustments to the settings can be achieved without having to access the sounder location. Changes can be made to all sounders by a single panel software download which saves time and reduces commissioning costs.


Reflective Sound Monitoring is employed to monitor the

audio output of the sounder. This is particularly beneficial

during regular weekly sounder tests.

RSM allows the system to listen for audibility whenever the

sounders are operated and the MZX Technology panel will

alert the user if any sounders fail to operate.

Failure of the beacon would also generate a fault at the MX

control panel.


Features and benefits:

  • High Output programmable sounder and sounder beacon
  • Loop Powered from MX Technology® Digital Loop
  • Indoor and Weatherproof outdoor versions available
  • Software programmable
  • 16 Tones
  • Integral Line Isolator
  • RSM Reflective Sound Monitoring
  • Visual alarm approved to EN 54-23 open category
  • Audible alarm approved to EN 54-3.

General information

Color

Red

Shape

Other

Length

108 mm

Width

108 mm

Height

100 mm

Uniclass

Pr_75_80_30_30 Fire alarm soundersPrimary

CAWS

S92/420 Alarm devices

Specification data - Fire alarm sounders

Standard

To BS EN 54-3 and EN 54-23.

Sounder type

Electronic sounder.

Rated voltage

Guidance for specification option:

  • Quiescent 0.45 mA.
  • Sounder Beacon 7.6–13 mA (dependent on volume and flash rate).

Enclosure protection

IP65.

Sound pressure level (minimum)

Selectable output volume of 90 or 103 dB.

Integral beacon

To BS EN 54-23, O.

Mounting

Surface.

RelativeHumidity

Up to 95% RH (non condensing).

Operating temperature

-20 to +70°C.

BIM objects

Platform Compatible Version
Revit
-

1

Literature

516.800.968 LPBS865 Open Class Symphoni Addressable Beacon Sounder IP65

516.800.968 LPBS865 Open Class Symphoni Addressable Beacon Sounder IP65

Similar products from ADT Fire and Security

LPAV865 Loop Powered Symphoni Addressable Sounder  Beacon IP65 Red Body Red Flash VID

LPAV865 Loop Powered Symphoni Addressable Sounder Beacon IP65 Red Body Red Flash VID

LPSY865 Loop Powered Symphoni Addressable Sounder IP65

LPSY865 Loop Powered Symphoni Addressable Sounder IP65

P82AVB Addressable OC Base Sounder Beacon

P82AVB Addressable OC Base Sounder Beacon