Verified by manufacturer 4 months ago
Certificate of constancy of performance
Certificate type
Addressable OC base sounder beacon.
Indoor direct ceiling applications. This unit can be used with the Ceiling Tile Adapter (CTA) kit (517.050.060) by using
the CTA Adaptor Plate, CTA-AP (517.050.058) available separately.
The FC442AVB Open Class Visual Alarm Device Sounder Beacon is a loop powered unit driven from an addressable control panel. The sounder has an integral two port loop short circuit isolator.
The product also has a base for fitting a fire detector, or alternatively a blanking cap can be used. Settings for the the 15 tones, white beacon flash rate and volume levels are all configurable using the control panel.
The selectable flash rates are as follows:
The light distribution is cylindrically symmetrical about an axis at a right angle (Alpha of 90°) to the surface on which the device is mounted, i.e. when the device is mounted on a horizontal ceiling, the light distribution is symmetrical about an axis extending vertically downwards through the centre of the device.
Color | Clear |
Finish | Semi-gloss |
Material | Polycarbonate |
Shape | Circle |
Warranty description | Three year |
Uniclass | |
CAWS | S92/420 Alarm devices |
Standard | To EN 54-17, EN 54-3, EN 54-23. |
Third-party certification | LPCB and BOSEC approved. |
Sounder type | Electronic sounder. |
Rated voltage | Loop voltage: 20–40 V, 35 V Typical. |
Enclosure protection | IP21C. |
Sound pressure level (minimum) | 60 dBA at 1 m. |
Integral beacon | To BS EN 54-23, O. |
Mounting | Surface. |
Power supply | From loop. |
RelativeHumidity | Up to 95% RH (non condensing). |
Operating temperature | -25 to +70°C. |
Accessories | 557.080.001 Blanking Cap For Sounder/VID/VAD Bases. 557.080.002 Conduit Adaptor For Sounder/VID/VAD Bases. |
Contains Red List materials | No |
Country of material origin | Czechia |
Country of product manufacture | Czechia |
Material | Polycarbonate |
Manufacturing plant location | |
Expected Life | Ten year |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|