Verified by manufacturer 17 days ago
EI240
Intumescent linear firestop seals for vertical and horizontal joints.
Suitable for vertical and horizontal joints in fire-rated walls and floors.
Test evidence does not cover applications at the Head of Wall.
Tenmat’s FF108 Linear Gap Seals are fully intumescent linear firestop seals tested to EN 1366-4. The durable seals are installed under compression and can accept up to 50% movement. They are equally suited to both vertical and horizontal joints. The seals offer up to 4 hour (EI240) fire rating for joints in fire rated walls and floors.
Features and benefits:
Color | Black |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | P12/35 Flexible intumescent gap sealer P12/330 Flexible intumescent gap sealer |
Size | 15 x 15 mm.Manufacturer guidanceMinimum floor slab depth of 250 mm. Minimum wall thickness of 250 mm. |
Fire performance | Floors: EI240; Walls: EI240. |
Seals | One seal required. Guidance for specification option: When installing in gaps/joints in floors, the product must be installed 25 mm down from the top of the floor slab. When installing in walls, the product must be installed centrally. |
Joints | Butted. Offset joints in adjacent seals by 500 mm (minimum). |
Platform | Compatible | Version |
---|---|---|