Suitable for vertical and horizontal joints in fire-rated walls and floors.
Test evidence does not cover applications at the Head of Wall.
Tenmat’s FF108 Linear Gap Seals are fully intumescent linear firestop seals tested to EN 1366-4. The durable seals are installed under compression and can accept up to 50% movement. They are equally suited to both vertical and horizontal joints. The seals offer up to 4 hour (EI240) fire rating for joints in fire rated walls and floors.
Features and benefits: