Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Verified by manufacturer 1 day ago

Single No Smoke Seals

A1S Group Variant:
Product certifications:
  • IFCC

    IFCC

    Certificate type

  • smas WORKSAFE

    smas WORKSAFE

    Certificate type

Vertical active fire and smoke curtain barrier providing up to 120 minutes integrity and EW120 radiation control, achieving 10.7 kW/m² at 120 minutes, tested to BS 8524-1 and installed to BS 8524-2.

Jump to:
BOS
+44 (0)1204 383839 Website

Application

Vertical active fire and smoke curtain barrier suitable for a wide range of internal fire compartmentation and smoke control applications, including protected means of escape, atria, lobbies, reception areas, corridor separation, openings in fire-resisting walls, boundary protection, escalators, stairwells, lift shafts and lift lobbies.

Regularly specified within hospitals and healthcare facilities, schools and universities, hotels, high-rise and mixed-use developments, commercial offices, retail environments, stadia, museums and galleries, as well as transport infrastructure, industrial and utility installations. Also suitable for defence, custodial, policing and secure environments where reliable fire and smoke containment is required.

Description

The Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier is an electrically operated, gravity fail-safe fire and smoke control system designed to form a virtually continuous fire-resisting barrier within a building. The system delivers 120 minutes fire integrity and EW120 radiation performance, maintaining radiation levels below 15 kW/m² and achieving 10.7 kW/m² at 120 minutes, supporting occupant tenability and protected means of escape strategies.

The barrier assembly comprises a carbon steel barrel and integrated 24 V d.c. electric motor, incorporating a high-performance flexible fire curtain fabric capable of withstanding temperatures in excess of 1000°C. Barrel deflection is compliant with BS 6323-5, ensuring stability and reliability across a wide range of opening sizes. A two-section bottom rail provides controlled descent, consistent tension and dependable gravity fail-safe deployment in the event of power or system failure.

The Flameshield EW120 system is designed for discreet architectural integration and can be concealed above ceiling lines. End plates, guides and hoods are available in a range of finishes, allowing the system to blend seamlessly with interior design requirements without compromising fire or smoke performance.

A two-stage closing operation, timed delay options and a comprehensive range of ancillary safety devices are available, including egress switches, access switches, obstruction detection and heat and smoke activation. All ancillary equipment is fully tested in accordance with Annex H of BS 8524-1. Optional audible and visual warning systems, including voice warning devices, enhance safety during deployment.

The system is fully compliance-tested, incorporates low-maintenance components, and is capable of full reset following fire testing without the need for specialist engineer attendance. Manufacture and construction align with tested assemblies and relevant sections of BS EN 16034, ensuring consistent performance and regulatory confidence.

Independent fire, radiation and smoke containment testing has been undertaken and approved by Warrington Fire Research Centre and Exova, in accordance with BS 8524-1, BS EN 1634-1 (fire resistance and radiation performance) and BS EN 1634-3 (smoke containment).

Features and benefits:

  • Gravity fail safe closes without mains power.
  • Provides smoke control.
  • Lightweight slimline compact design.
  • Two stage closing operation.
  • Compliance tested to maintain building fire safety and integrity in accordance with BS 8524-1 and installed in accordance with BS 8524-2.
  • Can be hidden neatly above the ceiling line to assist the building design and aesthetics.
  • Voice warning devices available.
  • Fully resets after fire test without the need for engineers to attend.
  • Low maintenance costs.
  • Timed delay closing.

Radiation:

  • 120 Minutes < 15 kW/m².
  • 15 Minutes - 2.617 kW/m².
  • 30 Minutes - 3.748 kW/m².
  • 60 Minutes - 6.306 kW/m².
  • 90 Minutes - 8.328 kW/m².
  • 120 Minutes -10.708 kW/m².

General information

Color

Other

Manufacturer guidance

Full selection of RAL colours available.

Finish

Powder-coated

Mill

Manufacturer guidance

C3 corrosion class available as standard. Advanced durability to corrosion class C3h on application.

Material

Carbon steel

Stainless steel

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

Extended warranty available on application.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

SKU Code

FS EW120

Specification data - Vertical active fire curtain barriers

Classification data

Standards

-

Barrier assemblies

To BS 8524-1.

Test standards

Vertical, horizontal and angled to BS EN 1634-1. BS EN 1634-3.

Third-party certification

Warrington Fire Report 406515.

Size

-

Manufacturer guidance

Maximum size (width x height): 8000 x 8000 mm. (32 m²). Insert requirements.

Performance

-

Smoke containment

No smoke seals.

Fire resistance

60 minutes.
120 minutes.

Accessories

Partial Drop.

Guidance for specification option:

The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes

Emergency Retract.

Guidance for specification option:

The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available.

BMS Interface.

Guidance for specification option:

The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed.

Single Photo Cell.

Guidance for specification option:

Tested and Passed by Exova to BS 8524-1 Annex H

Audio / Visual / Spoken Warning Unit.

Guidance for specification option:

The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An Audio / Visual / Spoken warning unit can be interfaced with this using power supplied by the primary / secondary source or via an external source.

Multi-beam Detection.

Guidance for specification option:

A multi-beam detection system is required when the barrier assembly is intended to protect a means of escape route. For more information, see BS 8524 - 2.5.8.5.2.

Fabric

4415-2-B1 fabric.

Guidance for specification option:

  • Stainless steel wire, reinforced glass fabric with a specially formulated intumescent fire retardant silicone elastomer.
  • Does not generate toxic emissions, and has a good resistance to hydrolysis.
  • At 140°C the coating system will form an expanding intumescent char.
  • The fabric has been independently tested for fire propagation in accordance with BS 476-6 in addition to this it also conforms to BS 476-7 which relates to surface spread of flame and in accordance with approved document B 2006.
  • As a requirement of BS EN 1634-1, the fabric and curtain are tested as a complete assembly in compliance with BS EN 1363-1 and BS EN 1363-2.

Barrel

Carbon steel tube.

Guidance for specification option:

Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.

Finishes

Powder-coated.
Mill.

Manufacturer guidance

C3 corrosion class available as standard. Advanced durability to corrosion class C3h on application.

Colour

-

Manufacturer guidance

Consult manufacturer and insert requirements. Full selection of RAL colours available.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Manufacturing plant location

Material

Carbon steel
Stainless steel

Expected Life

Ten year

Guidance for specification option:

Lifetime under BS 8524-2.

Manufacturer guidance

Lifetime under BS 8524-2.

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Product certifications

IFCC

IFCC

Fire and Smoke Curtain Installation and Servicing third party to BS 8524-2

smas WORKSAFE

smas WORKSAFE

SMAS 2025 (SSIP)

Literature

A1S Group Specification Sheet: Flameshield EW120

A1S Group Specification Sheet: Flameshield EW120

A1S Group Drawing (Face Fit) Flameshield EW120

A1S Group Drawing (Face Fit) Flameshield EW120

A1S Group Drawing (Reveal Fit) Flameshield EW120

A1S Group Drawing (Reveal Fit) Flameshield EW120

CPD materials

The Functionality, Design and Compliance of Fire and Smoke Curtains​

The Functionality, Design and Compliance of Fire and Smoke Curtains​

Case studies

Fire Curtains to EW120 for 125 Deansgate Manchester UK

Fire Curtains to EW120 for 125 Deansgate Manchester UK

Flameshield Fire Curtain with EW120 enhanced radiation control

Flameshield Fire Curtain with EW120 enhanced radiation control

Similar products from A1S Group

Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire Curtain

Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire Curtain

Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire Curtain

Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire Curtain

Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain

Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain