Verified by manufacturer 3 days ago

Sherwin-Williams

A two-component epoxy blast primer that can be overcoated after 30 minutes with FIRETEX® intumescent coatings offering a fast-track solution to off-site intumescent application.

Jump to:
+44 (0)1204 521771 Website

Application

A fast-track temporary protective for surfaces prepared by abrasive blast cleaning, designed for use under FIRETEX intumescent coatings.

Can be overcoated after 30 minutes with FIRETEX intumescent coatings offering a fast-track solution to off-site intumescent application.

Description

A two-component epoxy blast primer that can be overcoated after 30 minutes with FIRETEX® intumescent coatings offering a fast-track solution to off-site intumescent application.

General information

Color

Other

Guidance for specification option:

Redox.

Finish

Smooth

Material

Epoxy

Shape

Formless

Length

Bespoke

Width

Bespoke

Height

Bespoke

Uniclass

Pr_35_31_68_27 Epoxy resin coatingsPrimary

CAWS

M61/170 Off-site coating to galvanized steel

M61/160 Off-site coating to primed steel

M61/150 Off-site coating to unprimed steel

G10/660 Shop plus site painting

G10/640 Shop painting

SKU Code

FIRETEX® C69

Specification data - Epoxy resin coatings

Classification data

Colour

Redox.

Composition

Solvent-based.

Guidance for specification option:

Cleanser/ thinner No.5.

Volume solids

To ASTM-D2697-03, 41% ±2%.

VOC content

482 g/L determined practically in accordance with UK Regulations PG6/23.
537 g/L calculated from formulation to satisfy EC Solvent Emissions Directive.
420 g/kg content by weight from formulation, to satisfy EC Solvent Emissions Directive.

Flash point

Base: 4°C; additive: 4°C.

Density

1.278 kg/L.

Coverage

Theoretical: 12.83 m²/kg (16.40 m²/L).

Drying time

At +15°C: to touch: 15 minutes; to handle: 30 minutes; to recoat: 40 minutes.
At +23°C: to touch: 10 minutes; to handle: 20 minutes; to recoat: 15 minutes.

Application method

Airless or conventional spray.

Manufacturer guidance

Consult manufacturer's literature for full details.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Epoxy
Carbon dioxide equivalent

Carbon dioxide equivalent, as defined in BS EN 15804

Self-declared

Stage
Normalised unit (kg CO₂ eq/kg)
Declared unit (kg CO₂ eq/kg)
Stage:A1–A3 ('Production stage')
Normalised unit : 3.5 (kg CO₂ eq/kg)
Declared unit : 3.5

Lower emissions

Recyclability

0

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Literature

Fire Protection FIRETEX® C69 Product Data Sheet

Fire Protection FIRETEX® C69 Product Data Sheet

Similar products from Sherwin-Williams

Steel Protection Macropoxy® 400 - Multi-Functional Protection Coating

Steel Protection Macropoxy® 400 - Multi-Functional Protection Coating

Steel Protection Macropoxy® 4600 - Multi-Functional Protection Coating

Steel Protection Macropoxy® 4600 - Multi-Functional Protection Coating