NBS Source
I'm a manufacturer
Compare variants

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

Verified by manufacturer 15 days ago

Design .40 - With actuator BF 230-TN (BFL, BFN 230-T)

Mandik UK Limited Variant:
Third party certifications:
  • DoP

    DoP

    Certificate type

  • Hygiene requirements to VDI 6022

    Certificate type

  • Certificate of constancy of performance

    Certificate type

  • EPD

    EPD

    Certificate type

A multi-blade fire damper for HVAC ductwork.

Jump to:
0117 4526376 Website

Application

  • For use as a fire shutter without following air duct with cover grilles for closing ventilation openings in fire separating walls, constructions, elevator and other shafts, cable and other ducts, preventing the spread of heat and combustion products.
  • For use as a multi blade fire damper with following air duct on both sides (without cover grilles) or with duct on one side (with one cover grille), preventing the spread of heat and combustion products through this duct system.
  • Suitable for installation in solid wall construction, gypsum wall construction and solid ceiling construction.

Additional applications may be available, please reference product Technical Specifications for more detail.

Description

A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors.

Features and benefits:

  • Dimensions - from 200 x 300 to 1000 x 1000 mm.
  • CE certification according to EN 15650.
  • Tested according to EN 1366-2.
  • Classified according to EN 13501-3 + A1.
  • Fire resistance: EI 90 S, E 120 S.
  • Control of blades with electrical actuator 24 V or 230 V, initiated by thermal fuse.

General information

Color

Silver

Finish

Galvanized

Material

Steel

Shape

Rectangle

Square

Length

150 mm

Width

300 mm

315 mm

355 mm

400 mm

450 mm

Show more

Height

200 mm

250 mm

280 mm

300 mm

315 mm

Show more

Warranty description

Two year

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To EN 15650.

Test

To EN 1366-2.

Classification

To EN 13501-3.

Aerodynamic performance

To EN 1751.

Guidance for specification option:

Damper body: Class B; Damper blade: Class 3.

Arrangement

Multiblade.

Classification

EIS90.

EIS120.

Manufacturer guidance

Refer to the manufacturer's literature for placement and installation details to achieve the required fire resistance values.

Material

Zinc-coated steel.

Accessories

Microswitches for status indication.

Guidance for specification option:

Signalisation of damper blades position "OPEN" and "CLOSED".

Fusible links

-

Fusing temperature

72°C.

Guidance for specification option:

As standard.

95°C.

120°C.

140°C.

Spare fusible links

-

Manufacturer guidance

Insert requirements or omit.

Dimensions

-

Manufacturer guidance

  • Damper body: From 200 x 300 to 1000 x 1000 mm.
  • Construction length: 150 mm.

Due to the nature of multi-bladed dampers, bespoke sizing is not available; consult manufacturers technical specification for a full list of available sizes and insert requirements.

Actuator

Belimo BF 230-TN (BFL, BFN 230-T).

Guidance for specification option:

230 V a.c.

Manufacturer guidance

Fire dampers are equipped with Belimo spring return actuators with thermoelectric activation device BAT. The spring return actuator types are BFL, BFN or BF depending on the damper size.

Grille

Not required.

Guidance for specification option:

Installation as part of an air duct.

1 no. grille.

Guidance for specification option:

Following duct on one side.

2 no. grilles.

Guidance for specification option:

Fire shutter without following air duct.

Duct connection

Mandik FFDM breakaway joint.

Guidance for specification option:

FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained.

Refer to FFDM – Technical specifications for options and insert requirements.

Breakaway joint (supplied by others).

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Breakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper.

Sustainability data

Material

Steel

Third party certifications

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

DoP

DoP

FDML – Declaration of Performance

Hygiene requirements to VDI 6022

Hygiene requirements to VDI 6022

Hygienic assessment - Fire dampers

Certificate of constancy of performance

Certificate of constancy of performance

FDML – Certificate

EPD

EPD

Environmental Product Declaration - Fire Dampers

Literature

FDML – Technical specifications (130/17)

FDML – Technical specifications (130/17)

FFDM – Technical specifications (137/19)

FFDM – Technical specifications (137/19)

Similar products from Mandik UK Limited

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised  - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm)  - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper