NBS Source
I'm a manufacturer

ComPact NSX - Molded Case Circuit Breakers (MCCBs)

Verified by manufacturer 3 days ago

Schneider Electric Ltd

Schneider Electric's ComPact NSX range offer comprehensive circuit protection solutions designed for various power distribution needs. Distinct features tailored for different different applications.

Jump to:
+44 (0)870 608 8608 Website

Application

Molded case circuit breakers (MCCBs) suitable for the following applications:

  • Real estate.
  • Commercial buildings.
  • Healthcare.
  • Industrial buildings.
  • Data centres.
  • Utilities.
  • Transport.
  • Infrastructure.
  • Defence.
  • Temporary.
  • Public buildings.

Description

Suitable for medium-sized installations, the ComPact NSX range offers MCCBs with ratings up to 630 A. It features enhanced energy metering capabilities, enabling improved energy management and monitoring. The NSX is known for its compact size and efficient installation options.

Features and benefits:

  • Schneider Electric green signature style for the entire ComPact range.
  • Estimated 40% reduction of wiring time for panel builders.
  • Experience easier installation thanks to a new ergonomic front-plate design.
  • Gain the confidence that all auxiliaries are in the right spot, and check that the coil rating is correct.
  • Ergonomic new toggle for easier breaker manual operation.

Standards:

  • BS EN (IEC) 60947-2, BS EN (IEC) 60947-3, IEC 60664-1, BS EN (IEC) 60947-1, BS EN (IEC) 60947-4, BS EN (IEC) 60947-5.1, BS EN (IEC) 60947-4.1, UL(DuelCert), IEC 60364-8-1 Clause 8.3.1.1, IEC/EN 61000-4-2: electrostatic-discharge immunity tests.
  • b IEC/EN 61000-4-3: radiated, radio-frequency, electromagnetic-field immunity tests.
  • b IEC/EN 61000-4-4: electrical fast transient/burst immunity tests.
  • b IEC/EN 61000-4-5: surge immunity tests.
  • b IEC/EN 61000-4-6: immunity tests for conducted disturbances induced by radio-frequency fields.
  • b IEC/EN 61000-4-8: power frequency magnetic field immunity test.
  • b IEC/EN 61000-4-11: voltage dips, short interruptions and voltage variations immunity tests.
  • b CISPR 11: industrial.
  • b IEC 60068-2-1: dry cold at -55°C.
  • b IEC 60068-2-2: dry heat at +85°C.
  • Damp heat (tropicalization).
  • b IEC 60068-2-30: damp heat (temperature +55°C).

General information

Color

Black

Green

Warranty description

18 months

Uniclass

Pr_65_72_27_53 Moulded case circuit breakersPrimary

CAWS

V90/590 Equipment

Specification data - Moulded case circuit breakers

Standards

To BS EN IEC 60947-1 and BS EN 60947-2.

Third-party certification

To ISO 14025PEP and ISO 50001.

Rated operational current (Ie)

16 A.
25 A.
32 A.
40 A.
50 A.
63 A.
80 A.
100 A.
125 A.
160 A.
200 A.
250 A.
400 A.
630 A.

Number of poles

One.
Two.
Three.
Four.

Rated operational voltage (Ue)

220 V a.c.
240 V a.c.
380 V a.c.
415 V a.c.
440 V a.c.
500 V a.c.
525 V a.c.
660 V a.c.
690 V a.c.

Rated insulation voltage (Ui)

500 V a.c.
800 V a.c.

Rated impulse withstand voltage (Uimp)

8 kV.

Rated ultimate short circuit breaking capacity (Icu)

8 kA.
10 kA.
15 kA.
20 kA.
22 kA.
25 kA.
35 kA.
36 kA.
50 kA.
65 kA.
70 kA.
85 kA.
90 kA.
100 kA.
120 kA.
150 kA.
200 kA.

Rated service short circuit breaking capacity (Ics)

8 kA.
10 kA.
15 kA.
20 kA.
22 kA.
25 kA.
35 kA.
36 kA.
50 kA.
65 kA.
70 kA.
85 kA.
90 kA.
100 kA.
120 kA.
150 kA.
200 kA.

Utilization category

A.

Communications

-

Connectivity

Modbus.

Method of installation

Fixed.
Withdrawable.
Plug-in.

Accessories

Not required.
Auxiliaries.
Coils.
Handle.
Motor.
Terminal shields.
Connections.
Remote displays.

Similar products from Schneider Electric Ltd

ComPact NS - Molded Case Circuit Breakers (MCCBs)

ComPact NS - Molded Case Circuit Breakers (MCCBs)

ComPact NSXm - Molded Case Circuit Breakers (MCCBs)

ComPact NSXm - Molded Case Circuit Breakers (MCCBs)