NBS Source
I'm a manufacturer

Compare variants

PowerSand CBS / CBS Extra - Cement-Bound Sand
PowerSand CBS / CBS Extra - Cement-Bound Sand

Verified today

Heidelberg Materials UK

PowerSand CBS Extra

Verified today

Heidelberg Materials UK

PowerSand CBS

Summary
Cement-bound sand backfill materials designed for underground high-voltage cable installations.
Cement-bound sand backfill materials designed for underground high-voltage cable installations.
Application

Used as backfill in the installation of underground electricity cables.

Used as backfill in the installation of underground electricity cables.

Description

Cement-bound sand stabilised backfill materials as defined in ENA TS 97-1 for underground electricity cable installations.

Available in two variants:

  • PowerSand CBS: backfill material designed for underground high-voltage cable installations. It offers excellent thermal conductivity, compacts easily around cables, and helps dissipate heat to reduce electrical resistance.
  • PowerSand CBS Extra: high-performance, non-traditional stabilised backfill designed for power cable installations. It offers lower thermal resistivity than traditional CBS and contributes to a reduced carbon footprint.

Features and benefits:

  • Keeps cables cool due to low thermal resistance.
  • Consistent for ease of use and ultimate performance.
  • UKAS test certificates available if requested.
  • Meets or exceeds the requirements of ENA TS 97-1.

Cement-bound sand stabilised backfill materials as defined in ENA TS 97-1 for underground electricity cable installations.

Available in two variants:

  • PowerSand CBS: backfill material designed for underground high-voltage cable installations. It offers excellent thermal conductivity, compacts easily around cables, and helps dissipate heat to reduce electrical resistance.
  • PowerSand CBS Extra: high-performance, non-traditional stabilised backfill designed for power cable installations. It offers lower thermal resistivity than traditional CBS and contributes to a reduced carbon footprint.

Features and benefits:

  • Keeps cables cool due to low thermal resistance.
  • Consistent for ease of use and ultimate performance.
  • UKAS test certificates available if requested.
  • Meets or exceeds the requirements of ENA TS 97-1.
Color
Brown, Other
Brown, Other
Material
Sand, Cement, Concrete
Sand, Cement, Concrete
Shape
Formless
Formless

Specification

Classification data
Standard
Performance to ENA TS 97-1.
Performance to ENA TS 97-1.
Cement
Manufacturer's standard.
Manufacturer's standard.
Aggregates
-
-
Aggregate type
Sand.
Sand.
Nominal size (maximum)
4 mm.
4 mm.

Additional properties

Thermal performance
Resistivity: 0.75 Km/W.
Resistivity: 1.2 Km/W.
Third party accreditation
UKAS test certificates available (on request).
UKAS test certificates available (on request).
Dry density
Minimum of 1.6 mg/m³.
Minimum of 1.6 mg/m³.

Sustainability data

Contains Red List materials
No
No
Country of material origin
United Kingdom
United Kingdom
Country of product manufacture
United Kingdom
United Kingdom
Material
Sand, Cement, Concrete
Sand, Cement, Concrete
Carbon dioxide equivalent
Normalized unit
(kg CO₂ eq/kg)
A1–A3 ('Production stage') :
-
A1–A3 ('Production stage') :
-
Declared unit

Self-declared

A1–A3 ('Production stage') :
A1-A3 GWP Data provided upon request

Self-declared

A1–A3 ('Production stage') :
A1-A3 GWP Data provided upon request
Recyclability
100% Reclyclable
100% Reclyclable