Verified by manufacturer 29 days ago
Vertical fire curtain certified to 60 minutes integrity and radiation rating.
Suited to many different applications; some of the most common are to:
The Adexon-FC60EW is a multi-purpose fire curtain offering integrity (E) and radiation (W) performance. Designed to limit and control the spread of fire for 60 minutes at over 1000°C, and also reduce the radiation of heat from one side of the curtain to the other for 60 minutes. Smoke sealing is also available to limit and control the spread of smoke created by a fire.
Features and benefits:
Color | Other |
Finish | Galvanized Powder-coated |
Material | Steel Fiber-glass Polyurethane |
Shape | Rectangle |
Width | Bespoke 7000 mm 12000 mm Manufacturer guidanceCurtain maximum dimensions: 12 x 4.5 m or 7 x 8 m (width x height). |
Height | Bespoke 4500 mm 8000 mm |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | |
Barrier assemblies | CE marked to BS EN 16034. |
Test standards | Safety and performance to BS EN 16034, fire resistance to BS EN 1634-1 in accordance with BS EN 13501-2. |
Third-party certification | Applus+ Certificate 0370-CPR-6418. |
Size | Guidance for specification option:
|
Performance | |
Durability class | C1. |
Smoke containment | Not required.To BS EN 1634-3:2004.Guidance for specification option: Recommended option. Refer to manufacturer's literature for smoke control curtain sizes. |
Fire resistance | EW 60. |
Barrier units | Single.Multiple. |
Activation | Fire alarm signal.Signal from local smoke or heat detector.BMS. |
Accessories | None.Emergency retract buttons.Obstruction warning. |
Colour/ Finish | Galvanized. Galvanized and powder-coated. Guidance for specification option: All standard and non-standard PPC colours are available. Insert requirements. |
Bottom bar | Standard bar. Wide/ flat bottom bar. T-bar. |
Material | Steel Fiber-glass Polyurethane |