NBS Source
I'm a manufacturer

Vertical Fire Curtain - 180 min + Insulation - FC180EI - Fire Curtain

Verified by manufacturer 2 months ago

Adexon Fire & Smoke Curtains Third party certifications:
  • Fire Safety Certification

    Certificate type

Vertical fire curtain certified to 180 minutes integrity and insulation rating.

Jump to:
0151 422 9111 Website

Application

Suited to many different applications; some of the most common are:

  • Protected means of escape.
  • Insulation compartmentalisation.
  • Combustible areas.
  • Protecting fire-rated glazing.
  • Basement car parks.

Description

The Adexon-FC180EI is Adexon's highest specification curtain. It is designed to limit and control the spread of fire for 180 minutes at over 1000°C and stop the spread of heat from one side of the curtain to the other for 180 minutes. Adexon-FC180EI achieves the product rating of 180 minutes integrity (E) and 180 minutes insulation (I).


Features and benefits:

  • The system is tested and certified to BS EN 16034:2014.
  • Operation is via 24 V d.c. tubular motors controlled by an electronic control board.
  • The system is available in sizes up to 17 meters high and 22 meters wide to suit all site requirements.
  • It has gravity fail-safe to ensure that the system will deploy to its fire-operational position, so that protection is provided irrespective of whether power is maintained or not.
  • Standard lead time is between 6 to 10 weeks from approval of drawings.
  • Optional extras such as emergency retract buttons and obstruction warning are available upon request.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Steel

Fiber-glass

Polyurethane

Shape

Rectangle

Width

Bespoke

22000 mm

Guidance for specification option:

Maximum.

Height

Bespoke

17000 mm

Guidance for specification option:

Maximum.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

-

Barrier assemblies

CE marked to BS EN 16034.

Test standards

Safety and performance to BS EN 16034, fire resistance to BS EN 1634-1 in accordance with BS EN 13501-2.

Third-party certification

Applus+ Certificate AFP-1974.

Size

Guidance for specification option:

  • Curtain maximum dimensions: 22 x 17 m (width x height). Insert requirements or refer to a drawing.
  • Determine project requirements on a curtain-by-curtain basis through detailed design and scheduling. Refer to drawings for locations.

Performance

-

Durability class

C1.

Smoke containment

Not required.

To BS EN 1634-3:2004.

Guidance for specification option:

Recommended option. Refer to manufacturer's literature for smoke control curtain sizes.

Fire resistance

EI 180.

Guidance for specification option:

Requires a minimum water irrigation of 0.34 m3/h·m2 for all

curtain area.

Barrier units

Single.

Multiple.

Activation

Fire alarm signal.

Signal from local smoke or heat detector.

BMS.

Accessories

None.

Emergency retract buttons.

Obstruction warning.

Colour/ Finish

Galvanized.

Galvanized and powder-coated.

Guidance for specification option:

All standard and non-standard PPC colours are available. Insert requirements.

Bottom bar

Standard bar.

Wide/ flat bottom bar.

T-bar.

Sustainability data

Contains Red List materials

No

Material

Steel

Fiber-glass

Polyurethane

Third party certifications

Fire Safety Certification

Fire Safety Certification

Adexon-FC180EI Vertical Fire Curtain (Integrity & Insulation) - Certificate APF-1974 - SPC-117 -- EN 1634-1_2014+A1_2018 & EN 13501-2_2016 -- Exp 25,06,30

Literature

Fire Curtain Brochure FC180EI

Fire Curtain Brochure FC180EI

FC180EI Drawing

FC180EI Drawing

FC180EI Uniclass Spec

FC180EI Uniclass Spec

Similar products from Adexon Fire & Smoke Curtains

Concertina Fire Curtain - 120 min - CFC120E - Fire Curtain

Concertina Fire Curtain - 120 min - CFC120E - Fire Curtain

Vertical Fire Curtain - 120 min + Radiation - FC120EW - Fire Curtain

Vertical Fire Curtain - 120 min + Radiation - FC120EW - Fire Curtain

Vertical Fire Curtain - 120 min - FC120E - Fire Curtain

Vertical Fire Curtain - 120 min - FC120E - Fire Curtain

Vertical Fire Curtain - 60 min + Radiation - FC60EW - Fire Curtain

Vertical Fire Curtain - 60 min + Radiation - FC60EW - Fire Curtain

Vertical Fire Curtain - 90 min + Radiation - FC90EW - Fire Curtain

Vertical Fire Curtain - 90 min + Radiation - FC90EW - Fire Curtain