NBS Source
I'm a manufacturer

Underfloor Heating Mixing Shunt - 7021 - Mixing Shunt Pump

Verified by manufacturer 4 months ago

PETTINAROLI UK LIMITED Third party certifications:
  • EPD

    EPD

    Certificate type

Underfloor heating complete mixing kit with circulating pump, thermostatic valve with remote sensor and integrated non-return valve.

Jump to:
0121 3582012 Website

Application

Suitable for mixed temperature heating systems.

Description

The Pettinaroli 7021 mixing kit with single temperature setting point can solve is used for regulating the correct flow and supply temperature in hydronic floor heating systems. 


The Alpha2 pump is an electronic circulator, so is able to adjust the performances to the installation requirements. So the energy consumption will be reduced.


Thanks to the thermostatic head’s remote sensor, the 7021 it’s able to takes fluid from the primary heating circuit at high temperature (>55°C) and to mix it with the return to be able to supplies the secondary circuit with fluid at the right temperature (20–45°).


There is a built in non return valve to ensures correct direction of flow.


The remote sensor is placed in the sensor pocket.


Features and benefits:

  • EPD verified.
  • In accordance with ISO 14025:2006 and EN 15804:2012+A2:2019/AC:2021.

General information

Color

White

Yellow

Finish

Brass

Material

Brass

Plastic

Shape

Other

Width

157 mm

Warranty description

Two year

Uniclass

Pr_65_54_95_89 Thermostatic radiator valvesPrimary

CAWS

M42/340 Underfloor heating

S90/140 Direct hot water storage supply

S90/150 Indirect hot water storage supply

S90/680 Thermostatic mixing valves

Specification data - Thermostatic radiator valves

Arrangement

Remote sensor incorporating the selector.

Pattern

Straight.

Connections

1" Female BSP.

Guidance for specification option:

  • Pump ports diameter G1".
  • Manifold inlet/outlet G1".

Maximum temperature

80°C.

Manufacturer guidance

Max. liquid temperature.

Pressure

10 bar.

Manufacturer guidance

Max. system pressure.

Primary flow temperature

20–50 °C.

Length

130 mm.

Manufacturer guidance

Pump port-to-port length.

BypassFactor

0–800 L/h.

Flow rate (maximum)

Qmax ved ΔP =2 m H2O: 2.700 L/h.

Sustainability data

Contains Red List materials

Yes

Country of material origin

Italy

Country of product manufacture

Italy

Material

Brass

Plastic

Manufacturing plant location

Expected Life

15 year

Third party certifications

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

EPD

EPD

Environmental Product Declaration

Literature

7021 - Mixing Shunt for Hydronics underfloor heating

7021 - Mixing Shunt for Hydronics underfloor heating