Verified by manufacturer 9 months ago
TA10D3L0324TPE (32 A, 400 V; 100 A frame)
Range of triple-pole active automatic transfer switches.
Change source of supply.
Range of active automatic transfer switches.
Feature and benefits:
| Color | Black | 
| Shape | Rectangle | 
| Length | 94 mm Guidance for specification option: Depth. 95 mm 185.8 mm | 
| Width | 310 mm 351 mm 370 mm 467 mm | 
| Height | 147 mm 164 mm 341 mm | 
| Uniclass | 
| SKU Code | TA10D3L0324TPE, TA10D3L0404TPE, TA10D3L0504TPE, TA10D3L0634TPE, TA10D3L0804TPE, TA10D3L1004TPE, TA16D3L0804TPE, TA16D3L1004TPE, TA16D3L1254TPE, TA16D3L1604TPE, TA25D3L1002TPE, TA25D3L2502TPE, TA25D3L2004TPE, TA25D3L2504TPE, TA63D3L6302TPE, TA63D3L3204TPE, TA63D3L4004TPE, TA63D3L5004TPE, TA63D3L6304TPE | 
| Classification data | |
| Standards | To IEC 60947-6-1. | 
| Short-circuit capability | PC. | 
| Method of controlling transfer | ATSE. Guidance for specification option: Automatic and manual operation available. | 
| Operating mechanism | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Rated operational voltage (Ue) | 400 V a.c. | 
| Rated impulse withstand voltage (Uimp) | 6 kV. Guidance for specification option: Switch and controller. | 
| Rated insulation voltage (Ui) | Switch: 800 V. Controller: 500 V. Guidance for specification option: Switch. | 
| Rated operational current (Ie) | 32 A. | 
| Utilization category | AC-33B. | 
| Rated operational frequency | 50/ 60 Hz. | 
| Number of poles | Triple. | 
| Rated short-time withstand current (Icw) | 5 kA during 0.1 s. | 
| Rated short-circuit making capacity (Icm) | 15 kA switch-disconnector alone 400 V a.c. at 50 Hz. 75 kA with upstream protection circuit breaker 400 V a.c. at 50 Hz. | 
| Service conditions | Normal. | 
| Terminals | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Controls | |
| Type | Four push buttons. | 
| Display type | Liquid crystal display (LCD). | 
| Illuminated display to indicate the following conditions | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| User-adjustable functions | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Features | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Communication module | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Enclosure | |
| Ingress protection (minimum) | Front face: IP40 auto mode. Inside the enclosure: IP20 manual mode. | 
| Impact protection (minimum) | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Material | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Finish | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. | 
| Colour | Black. | 
| Net weight | 3.4 kg. | 
| Dimensions | 147 x 310 x 94 mm. Guidance for specification option: Height x width x depth. | 
| Mounting | Fixed - plate. Fixed - DIN rail. | 
| Locking options | Padlock in OFF position. | 
| Third-party certification | CE; CB; CCC. | 
| Ambient temperature | Air temperature for operation: -25 to +70°C. Air temperature for storage: -35 to +85°C. | 
| Frame | 100 A. | 
| Durability | Mechanical: 8000 cycles. | 
| Accessories | Not required. TPCDIO05 function module - load shedding and availability warning. Guidance for specification option: Output signal. 
 TPCDIO07 function module - transfer inhibit and remote testing. Guidance for specification option: Input signal. 
 TPCDIO08 function module - voluntary remote control. Guidance for specification option: Input signal. 
 TPCDIO10 function module - fire protection; 24 V d.c. pulse. Guidance for specification option: Input signal. 
 TPCDIO11 function module - fire protection; 24 V d.c. constant. Guidance for specification option: Input signal. 
 TPCDIO13 function module - fire protection; 230 V a.c. constant. Guidance for specification option: Input signal. 
 TPCDIO14 function module - fire protection; dry contact; passive. Guidance for specification option: Input signal. 
 TPCDIO17 function module - genset start and alarm. Guidance for specification option: Output signal. 
 Manufacturer guidanceSignalling accessories/ devices. |