Verified by manufacturer 3 months ago
Steel - Polyester lacquer
Partition with a metal facing and an aluminium honeycomb core.
The ST60 partition is designed for ultra-clean rooms that must be kept completely free of microbiological contamination. The partition consists of non-combustible modular panels, 60 mm thick, manufactured from time-stable materials and no emitting particles. The partition provides smooth surfaces which are easy to clean, are airtight and offer good insulation.
Profiles integrated into the thickness of ST panels allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full-length grooves on both sides of the wall panels.
Features and benefits:
Components:
Color | White |
Finish | Polished Lacquered |
Material | Metal Carbon steel Guidance for specification option: Coated Aluminium Guidance for specification option: Honeycomb |
Shape | Rectangle |
Length | 4000 mm 6000 mm |
Width | 200 mm 250 mm 350 mm 550 mm 800 mm |
Uniclass | |
CAWS | K30/10 Relocatable partition system K30/130 Relocatable partition system K30/135 Relocatable partition/ ceiling system |
Panel partitioning | Partition panels. |
Joint treatment | Bi-component polyurethane adhesive. |
Joint finish | MS polymer caulk (for VOC free installation) and silicone sealant. |
Width | 200 mm. 250 mm. 350 mm. 550 mm. 800 mm. |
Panel length | 4000 mm. 6000 mm. |
Facing | Steel sheet S280 GD, hot-dip galvanized Z225. Guidance for specification option: 225 g/m² of zinc on the two faces or similar. |
Sheet facing thickness | 0.5 mm. 0.6 mm. Guidance for specification option: Standard. 0.8 mm. |
Colour/ Finish | Polyester 25 μm lacquer. Guidance for specification option: Class in accordance with XP P 34-301: llla. |
Thickness | 60 mm. |
Profile | Metallic profile for passage of cables. |
R-Value | 1.6. |
Weight | Weight 10.7 kg/m² (two faces, 0.5 mm thick steel); 6.9 kg/m² (two faces, 0.67 mm aluminium). |
Air tightness | Qs ≤0.0027 m³/h.m² under ΔP: 50 Pa. Manufacturer guidanceTightness in the whole partition with silicone joint. |
Reaction to fire | Euroclass A2-s1,d0. |
Approvals | FM Global approval: FM Approvals (standard 4880) = Class 1; UL approval (cable routing) Safety E471046. |
Country of product manufacture | France |