Smoke curtain available in a number of standard sizes.
Suitable to be used to form a virtually continuous barrier against smoke.
An electrically operated active smoke curtain barrier assembly used to form a virtually continuous barrier against smoke. Barrier assemblies comprise a metallic fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm (0.047 in) thick stainless steel box. A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.
The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position. Barrier assemblies have been tested to the requirements of BS EN 12101:2006, Annex B for ‘Reliability and response times’ (1000 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.15 m/s). Barrier assemblies have been tested to the requirements of BS EN 12101:2006, Annex C for ‘Permeability of materials to smoke’ (0.3 m3/h/m2. Barrier assemblies have been tested to the requirements of BS EN 12101-1:2006, Annex D for ‘Temperature/ Time Resistance Tests’ (120 minutes integrity).
Period of Fire Resistance:
120 minutes (2 hours) integrity.
Certification:
Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012. Complete barrier assemblies are certified with an independent accredited certification body operating an accredited United Kingdom Accreditation Service (UKAS) scheme for installation, commissioning and servicing.
Operation:
Barrier assemblies commence movement upon initiation of BMS alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.
In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. During this period, the SmokeStop® D600A active smoke curtain barrier assembly will deploy on receipt of a signal. At the end of the period, the Barrier assembly will deploy.
Product certification, performance and/ or testing:
Approving standards:
The following standards apply to this product:
Finish | Galvanized Powder-coated |
Material | Fabric Guidance for specification option: Flexible metallic fabric. |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: From date of commissioning. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | BS EN 12101-1+A1, BS EN 1363-1, BS EN 1634-3, BS EN 13501-4, BS EN ISO 1716, BS EN 13823, BS EN 13501-1, BS 476-6, BS 476-7. |
Barrier assemblies | To BS EN 12101. |
Test standards | To BS EN 12101. |
Third-party certification | CE Marked, Warrington fire, Certifi. |
Size | Bespoke.Guidance for specification option: Consult manufacturer and insert requirements. |
Performance | |
Pressure and impact | SD. |
Durability class | C1. |
Smoke containment | To BS EN 12101. |
Fire resistance | To BS EN 13501-4, 120 minutes (2 hours) integrity. |
Reaction to fire | To BS EN 13501-4. |
Barrier units | Single.Multiple. |
Deployment | Full.Partial.Split drop delay. |
Side channels | End fixed. Recessed fixed. Guidance for specification option: Recommended 5 mm gap between side guide and building material. |
Concealment | Flush fit. Suspended ceiling with recessed shadow gap. Suspended ceiling with patented SLAT™. Guidance for specification option: Self levelling access trim. |
Fixing | Face fixed. I beam. Soffit fixed. Unistrut and drop rods. |
Arrangement | Upside down. Vertical. |
Opening sizes | Guidance for specification option: Insert requirement. |
Frame colour/ finish | Galvanized. Powder coated. Guidance for specification option: Insert colour requirement. |
Classification | D120, D600A, A2-s1, d0, Class '0'. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | Coopers Fire offer a take back service where product is broken down into component parts. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 8 | |
Revit 2017 | 8 |
Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel
Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina
Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain
Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain