Partitioning systems incorporating GTEC Fire gypsum board, fixings, frame and finishing products. Suitable for use across many construction sectors, including commercial, residential, education and health. They offer a simple, lightweight, durable and versatile means of dry wall construction.

General information
Specification data
Product Reference

Siniat GTEC Fire Board Partition Systems

Partition type

RFP 016: C Stud Partition

System weight: 42 kg/m²; Thickness: 100 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 52 dB sound reduction.

RFP 038: Twin Frame Partition

System weight: 52 kg/m²; Thickness: 200 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 62 dB -7 Ctr sound reduction.

RFP 044: C Stud Partition

System weight: 26 kg/m²; Thickness: 100 mm; Fire performance: 60 minutes; Strength duty: Heavy; Acoustic performance: 47 dB sound reduction.

RFP 045: C Stud Partition

System weight: 50 kg/m²; Thickness: 130 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 48 dB sound reduction.

RFP 046: C Stud Partition

System weight: 51 kg/m²; Thickness: 130 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 56 dB sound reduction.

RFP 050: C Stud Partition

System weight: 42 kg/m²; Thickness: 120 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 53 dB sound reduction.

RFP 054: C Stud Partition

System weight: 42 kg/m²; Thickness: 120 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 46 dB sound reduction.

RFP 062: C Stud Partition

System weight: 26 kg/m²; Thickness: 176 mm; Fire performance: 60 minutes; Strength duty: Heavy; Acoustic performance: 42 dB sound reduction.

RFP 076: C Stud Partition

System weight: 43 kg/m²; Thickness: 196 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 57 dB sound reduction.

RFP 127: C Stud Partition

System weight: 26 kg/m²; Thickness: 120 mm; Fire performance: 60 minutes; Strength duty: Heavy; Acoustic performance: 40 dB sound reduction.

RFP 134: C Stud Partition

System weight: 42 kg/m²; Thickness: 140 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 48 dB sound reduction.

RFP 135: C Stud Partition

System weight: 42 kg/m²; Thickness: 140 mm; Fire performance: 120 minutes; Strength duty: Severe; Acoustic performance: 56 dB sound reduction.

System height

As drawing

Insert reference.

Jointing

Insert requirement(s) from manufacturer's literature.

Sealer

GTEC Drywall Sealer

Ivory, pre-decoration coat for plasterboard.

GTEC Universal Sealer

For use on plasterboard prior to painting for improved whiteness and covering power.

Accessories

None

GTEC V-Brace

For RFP 038 only, 1500 mm centres.

Standard product features

GTEC Fire Board:

  • Material: Aerated calcium sulfate di-hydrate with fire-resisting fillers and fibres enclosed inside a tough pink paper with bound edges. Core and papers are bonded with starch. PVA edge glue.
  • Size (w x l): 900–1200 x 1800–3000 mm.
  • Nominal weight: 10.2–12.3 kg/m².
  • Thermal resistance (R-value): 0.05–0.06 m²K/W.
  • Thermal conductivity (K-value): 0.24–0.25 W/mk.

GTEC Intumescent Acoustic Sealant:

Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance.

GTEC Corner and Edge Beads:

Provides corner and edge reinforcement.

GTEC Socket Pad:

Maintains acoustic and fire integrity at sockets.

GTEC Insulation Hold:

Secures insulation to prevent slump.

Fixings:

GTEC Self-Tapping Drywall Screws.

Product Options

Partition type:

- RFP 016: C Stud Partition:

  • Facing inner layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS50Rx C studs at 600 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 038: Twin Frame Partition:

  • Facing inner layers: One 15 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 15 mm-thick GTEC Fire Board both sides.
  • Studs: Twin GTEC CS50Rx C studs at 600 mm centres. GTEC V-Brace at 1200 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 044: C Stud Partition:

  • Facing outer layers: One 15 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS70Rx C studs at 600 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 60 minutes.
  • Strength duty rating (to BS 5234-2): Heavy.

- RFP 045: C Stud Partition:

  • Facing inner layers: One 15 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 15 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS70Rx C studs at 600 mm centres.
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 046: C Stud Partition:

  • Facing inner layers: One 15 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 15 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS70Rx C studs at 600 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 050: C Stud Partition:

  • Facing inner layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS70Rx C studs at 600 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 054: C Stud Partition:

  • Facing inner layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS70Rx C studs at 600 mm centres.
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 062: C Stud Partition:

  • Facing outer layers: One 15 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS146Rx C studs at 600 mm centres.
  • Fire performance (to BS 476-22 and BS EN 1364-1): 60 minutes.
  • Strength duty rating (to BS 5234-2): Heavy.

- RFP 076: C Stud Partition:

  • Facing inner layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS146Rx C studs at 600 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 127: C Stud Partition:

  • Facing outer layers: One 15 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS90Rx C studs at 600 mm centres.
  • Fire performance (to BS 476-22 and BS EN 1364-1): 60 minutes.
  • Strength duty rating (to BS 5234-2): Heavy.

- RFP 134: C Stud Partition:

  • Facing inner layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS90Rx C studs at 600 mm centres.
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

- RFP 135: C Stud Partition:

  • Facing inner layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Facing outer layers: One 12.5 mm-thick GTEC Fire Board both sides.
  • Studs: Single GTEC CS90Rx C studs at 600 mm centres.
  • Insulation: 25 mm-thick 16 kg/m³ glass mineral wool (supplied by others).
  • Fire performance (to BS 476-22 and BS EN 1364-1): 120 minutes.
  • Strength duty rating (to BS 5234-2): Severe.

System height (maximum):

3.3–8 m (dependent on system build-up).