Roda Phoenix Extractor - AOV Smoke vent SHEV

Verified by manufacturer 17 days ago

P--3-S1-S

Lamilux Rooflights Ltd Variant:
Third party certifications:
  • TUV - Safety and Quality Report

    Certificate type

Natural heat and smoke extractor and ventilator panel.

Jump to:
+44 (0)1284 749051 www.lamiluxskylights.co.uk

Application

  • Flat roofs.
  • Northlight roofs.
  • Skylight systems.
  • Gable roof skylight systems.

Description

In addition to its function as a natural heat and smoke extractor, the PHOENIX can be used for everyday ventilation, even coping with extreme weather conditions. The top flaps can be fitted with a choice of either 16 mm multiwall polycarbonate panels or an aluminium sandwich structure. Depending on the top flap infill, sound absorption levels of up to 33 dB RW are possible.


Features and benefits:

  • Flexible sizing.
  • Suitable for use on flat roofs.
  • Suitable for everyday ventilation (full ventilation at 90° vent position).
  • Endurance tested to 10,000 opening cycles.
  • The thermally separated version reduces condensation.
  • Good aerodynamic efficiency.
  • Good U-value and low joint leakage.
  • Available with opaque flaps.
  • Efficient drainage of rainwater via central drainage channels.
  • Energy-saving natural lighting.
  • Hail- and fall-through-proof depending on the specification.
  • Powder coating allows for individual choice of colours.
  • Plinth mounting using tension locks – no drill holes needed.
  • Maintenance-free hinges are made from aluminium castings with stainless steel shafts.
  • Easy mounting in all roof constructions up to a 90° slope.

General information

Color

Other

Finish

Mill

Material

Aluminium

Polycarbonate

Shape

Square

Rectangle

Length

Bespoke

Width

Bespoke

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary
Pr_30_59_72_31 Framed rooflights

CAWS

L10/45 Rooflights

L10/460 Rooflights

L10/490 Roof ventilators

Product range

Smoke ventilation

Specification data - Natural smoke and heat exhaust ventilators

Standard

To EN 12101-2.

Opening type

Double flap.

Mounting

Roof-mounted.

Roof-mounted (flat roof), gable roof skylight systems, skylight systems, northlight roofs.

Aerodynamic free area

Non-standard sizes are available on request.

1 m².

Reliability classification

Re 1000.

VdS approval minimum Re 50.

Snow load classification

Up to SL 1500.

Low ambient temperature classification

T (-15).

Wind load classification

Up to WL 3000.

VdS approval minimum 1500 N/m².

Resistance to heat classification

B 300-E.

300 °C / fire-resistance rating E.

Arrangement

Aluminium or polycarbonate panels.

Dimensions

-

Length

1500 mm.

Width

1050 mm.

Controls

SHEV fitting - 24 V d.c. motor 2.0 A.

Opening angle approximately 90°.

Materials

-

Ventilator

-

Frame

Aluminum.

Glazing

Aluminium alloy (AlMgSi05). Inclined at 6° to the horizontal.

Attached using three hinges with carriage bolts.

A3 - Double-skin aluminium version.

K3 - 16 mm / 3 wall clear polycarbonate panels.

Finish

Mill finish.

Accessories

None.

Timer for night cooling.

Wind and rain sensors for protection against bad weather.

Sound insulation

Up to Rwp 33 dB.

Hinges

Panels secured with burglar-proof carriage bolts onto three hinges.

Environmental information

Contains Red List materials

No

Country of product manufacture

Germany

Literature

roda Pheonix data sheet

roda Pheonix data sheet

LAMILUX Roda double flap system for nshev brochure

LAMILUX Roda double flap system for nshev brochure

LAMILUX Roofs of Light Brochure

LAMILUX Roofs of Light Brochure

Third party certifications

TUV - Safety and Quality Report

TUV - Safety and Quality Report

ISO 9001 : 2015

TUV - Safety and Quality Report

TUV - Safety and Quality Report

ISO 50001:2011

Similar products from Lamilux Rooflights Ltd

Continuous Barrel Vault Rooflight B

Continuous Barrel Vault Rooflight B

Glass Roof PR60

Glass Roof PR60

Glass Roof PR60 Passivhaus

Glass Roof PR60 Passivhaus

Glass Skylight F100 - rooflight

Glass Skylight F100 - rooflight

Glass Skylight F100 Circular - rooflight

Glass Skylight F100 Circular - rooflight

Glass Skylight FE 3° - rooflight

Glass Skylight FE 3° - rooflight

Glass Skylight FE Circular - rooflight

Glass Skylight FE Circular - rooflight

Glass Skylight FE Passivhaus - rooflight

Glass Skylight FE Passivhaus - rooflight

Glass Skylight Pyramid / Hipped  - rooflight

Glass Skylight Pyramid / Hipped - rooflight

Roda Louvre Window - AOV Smoke vent SHEV

Roda Louvre Window - AOV Smoke vent SHEV