QA Certificate
Certificate type
Preformed pipe insulation for thermal, acoustic and fire stopping applications.
Preformed pipe insulation for thermal and fire stopping insulation to HVAC pipework.
Suitable for heating and ventilation pipes in a range of settings, through buildings, plants and other structures.
ROCKWOOL H&V Pipe Sections have been successfully tested for providing fire stopping to steel and copper pipe penetrations where they penetrate fire resistant walls and floors.
Suitable for heating and ventilation pipes in a range of settings, through buildings, plants and other structures.
Features and benefits:
Resistance to fire performance:
Tested to BS EN 1366-3, for the fire resistance of penetration seals offering up to EI 120.
Material | Stone wool |
SizeRefer to manufacturer's literature for sizing information. | - |
Uniclass | |
CAWS | S90/570 Insulation to pipelines T90/450 Insulation to pipelines to control heat loss |
Standard | To BS EN 14303, ISO 14001. |
Thermal conductivity | 0.033–0.034 W/m·K. |
Finish | Aluminium foil faced. |
Reaction to fire classification | A2-s1,d0. |
Insulation thickness (minimum) | 20 mm.25 mm.30 mm.35 mm.40 mm.45 mm.50 mm.55 mm.60 mm.65 mm.70 mm.75 mm.80 mm.90 mm.100 mm. |
Execution | Installing foil faced mineral wool insulation on pipelines. |
Pipe diameterInsert requirements, 17–406 mm. Refer to manufacturer's literature for sizing information. | - |
Specific heat | 0.84 kJ/kg·K (nominal) at 20°C. |
Density | 120 kg/m³. |
Length | 1000 mm. |