QRS75
CE Marking
Certificate type
Intumescent vent duct fire sleeves to prevent the spread of fire, where either rectangular or circular plastic plastic ducts penetrate fire compartment walls.
Intumescent vent duct fire sleeves to prevent the spread of fire, where either rectangular or circular plastic plastic ducts penetrate fire compartment walls.
The QRS Fire Sleeve consists of a continuous pressed steel shell containing a high performance graphite based intumescent material which reacts under the influence of heat to exert pressure on the plastic vent duct as it softens to form a carbonaceous char which provides an effective insulation plug thus preventing fire passing through to the adjoining compartment.
The QRS is manufactured specifically to suit differing sizes and diameters of duct and is supplied ready to be fitted into the wall with an opening lid for retrofitting.
Durability
Tested to Type X durability which means the QRS Intumescent Fire Sleeves can be installed in conditions exposed to weathering.
Features and benefits:
Standards and approvals:
Installation:
Quelfire QRS CE Marked Intumescent Fire Sleeves should be used where a plastic ventilation duct penetrates a fire rated wall to maintain the compartmentation in the event of a fire.
The QRS requires no mechanical fixing or framework support, they rely on the fire rated wall construction, plasterboard or solid masonry/block (or QuelStop Fire Batt) to hold it in place so the penetrations should be cut as tight as possible to the QRS Fire Sleeve itself, suggested approximate apertures sizes are given in the “performance” table in the associated "Product Data Sheet".
For the simplest installation, the QRS Fire Sleeve should be installed around the duct and then the wall installed tight around the QRS, however, they can be retrofitted into the wall too.
Simply hinge open the lid, feed around the duct, wrap tight and close the lid, secure shut with the self-adhesive tape supplied (or self tapping screw in the case of circular fire sleeves) and then slide the QRS along the duct into the wall construction.
The QRS should be installed centrally positioned within the wall and must be either flush or protruding from both sides of the wall in accordance with the relevant installation detail.
Once installed into the wall, in the correct position, the perimeter should be sealed with QuelStop Intumescent Acoustic Acrylic Sealant.
Where oversize hole or letterboxes with other services are formed then the QRS Fire Sleeve can be installed in conjunction with the QuelStop Fire Batt system having been tested in various wall constructions including with multiple ducts/QRS stacked or side by side.
Where a cluster of ducts/QRS are installed the QRS should be tight to each other, alternatively they need to be far enough apart to suitably install QuelStop Fire Batt or the original wall construction, all in accordance with the specific installation detail and tested scope of application.
A full set of installation details and a step by step guide are available and we recommend you check all available data before commencing installation.
For full details of the tested scope of application and for installation details, please refer to the associated document "Installation Instructions".
Color | Black Guidance for specification option: Grey-black. |
Finish | Galvanized |
Material | Intumescent Guidance for specification option: Steel shell containing graphite based intumescent material. Steel |
Shape | Circle Guidance for specification option: Cylindrical. Rectangle |
Length | 180 mm 140 mm |
Width | 110 mm 204 mm 220 mm 75 mm 90 mm |
Height | 54 mm 60 mm 90 mm |
Uniclass | |
CAWS | P12/43 Pipe collar P12/370 Pipe collar |
Material | Galvanized mild steel shell.Guidance for specification option: Containing graphite based intumescent material. |
Form | Grey-black solid laminate encased in circular/ rectangular mild steel shell. |
Type | Circular, semi-rigid ducts. |
Solubility in water | Insoluble in water and generally chemical inert. |
Upper temperature stability | Expands greatly if heated above 200°C. |
Reaction to fire | Class F. Guidance for specification option: To EN 13501-1. |
Length | 140 mm. Manufacturer guidanceCustom lengths are available on request; contact manufacturer for details. |
Dimensions | 75 mm diameter. |
FireRating | 120 min. Guidance for specification option:
|
Country of product manufacture | United Kingdom |
Material | Intumescent Guidance for specification option: Steel shell containing graphite based intumescent material. Steel |