Verified by manufacturer 23 days ago
FS600HPEFP – 600 ml
A fire resistant, intumescent sealant.
Application / Use:
Reinstates the fire resistance performance in a wall or floor around combustible penetration services. Pyropro HPE can be used in conjunction with Stopseal Batt system, please refer to tested details.
Pyropro HPE is a fire resistant, intumescent sealant for
interior penetration seals. It is designed to provide a
high-volume expansion and pressure seal during a fire for
areas where combustible services penetrate apertures in
floors and walls that are designed to provide
compartmentation.
Color | Grey |
Finish | Matt |
Material | Acrylic Guidance for specification option: Graphite based PVA/acrylic intumescent sealant. |
Shape | Formless |
Uniclass | |
CAWS | F30/610 Movement joints with sealant F30/670 Head of non-loadbearing walls F30/76 Movement joints with sealant K10/125 Metal stud partition system K10/15 Lining on timber K10/155 Wall lining system (metal studs) K10/165 Wall lining system (metal framing) K10/175 Wall lining system (metal furrings) K10/185 Wall lining system (adhesive) K10/205 Lining on timber K10/215 Suspended ceiling system K10/220 Proprietary suspended ceiling system K10/245 Ceiling lining on timber K10/25 Ceiling lining on timber K10/30 Metal stud K10/35 Wall lining system (metal framing) K10/41 Wall lining system (metal furrings) K10/45 Wall lining system (adhesive) L10/75 Sealant joints L10/810 Sealant joints L20/820 Sealant joints P12/370 Pipe collar P12/390 Sealant P12/43 Pipe collar P12/47 Sealant P12/48 Sealant – fire-resisting acrylic |
Product range |
Standard | To BS EN 1366-3:2009, BS EN 1026:2000, ASTM E84, AS 1530.4 2014, BS EN 13501-2:2016, LEED 4.1; BS EN ISO 10140-2:2020. |
Third-party certification | UL-EU-00770-CPR, UAE CoC ENCG.R38118 UL-EU-00770, CE Marked ETA-20/1011, Emicode EC 1+ and ISO 9001: 11378. |
Sealant type | Graphite based PVA/ acrylic intumescent sealant. |
Colour | Anthracite grey. |
Fire performance | |
Fire resistance | To BS EN 1366-3:2009 Fire resistance tests for service installations.Guidance for specification option: Penetration seals See UL-EU 00770 for fire resistance performance. BS EN 13501-2:2016 Fire classification of construction products and building elements. See UL-EU 00770 for fire resistance performance |
Density | ~1.35 g/cm³. |
Application temperature | +5℃ to +35℃. Guidance for specification option: For unopened material, store in a well-ventilated, dry, cool environment. Recommended temp ranges +5°c - +35°c. Protect against exposure to direct sunlight. Always ensure that safe manual handling procedures are followed at all times. |
Drying time | ~40 minutes (23°C and 50% relative humidity). |
Air permeability | To BS EN 1026:2000, 600 Pa. Guidance for specification option: BS EN 1026:2000 Windows and doors. Air permeability. Test method. Tested at 600 Pa (contact technical.fsi.uk@etexgroup.com for details). |
Acoustic performance | To BS EN ISO 10140-2:2020, up to 62 dB. Guidance for specification option: BS EN ISO 10140-2:2020 Laboratory measurement of sound insulation of building elements. Measurement of airborne sound insulation Up to 62dB achievable Contact technical.fsi.uk@etexgroup.com for details. |
Shelf life | 18 months. |
Shore A hardness | To BS ISO 7619-1:2010, 85/81 (1 second/ 5 seconds). Manufacturer guidance(28 days) |
VOC content | LEED 4.1 NC-2009 IEQc4.1 Guidance for specification option: Low-Emitting Materials—Adhesives and Sealants. Contact technical.fsi.uk@etexgroup.com for details. |
Chemical resistance | Manufacturer guidanceNot to be used where joints are to be constantly immersed in water. Do not use on substrates that are likely to release solvents, oils or plasticizers. Not resistant to water, strong acids, strong bases, oxidizing agents (i.e hydrogen peroxide), alcohols, hydrocarbon solvents. |
Unit size | 600 ml. |
Country of product manufacture | United Kingdom |
Material | Acrylic Guidance for specification option: Graphite based PVA/acrylic intumescent sealant. |
Manufacturing plant location |