Verified by manufacturer 11 days ago
Central Safety Power Supply Systems (CSPSS) - 10–30 kV·A
A range of uninterruptible power supply (UPS) systems for businesses, institutions and critical infrastructure.
Legrand offers a comprehensive range of Uninterruptible Power Supply (UPS) systems designed for businesses, institutions and critical infrastructure.
The range includes Single Phase UPS Systems, Three Phase UPS Systems, and Central Power Supply Systems (CPSS).
Color | Black White |
Finish | Other |
Material | Other |
Shape | Rectangle |
Length | 513 mm 440 mm 557 mm 600 mm 500 mm |
Width | 440 mm 170 mm 414 mm 600 mm 900 mm |
Height | 44 mm 88 mm 132 mm 238 mm 1370 mm |
Warranty description | Two year |
Uniclass | |
CAWS | W53/380 Power supply units W53/380 Power supply units |
SKU Code | 0 |
Classification data | |
Standards | To BS EN IEC 62040-1, BS EN IEC 62040-2, BS EN IEC 62040-3, and EN 50171. |
Mode of operation | On-line. |
Configuration | Manufacturer guidanceInsert requirements. |
Efficiency | |
Overall (minimum) | Up to 96%. |
Eco mode (minimum) | 99%. |
Input | |
Nominal voltage | Three-phase 400 V a.c./ single-phase 230 V a.c. Guidance for specification option: 380, 400, 415 3F+N+PE (o 220, 230, 240 1F). Standard configurations with 3-3 distribution (multi IN/OUT settings available upon request). |
Voltage tolerance | +15%/-20%. |
Frequency | 45–65 Hz. |
Power factor | > 0.99. |
Total harmonic distortion (THD) | < 3% at full load. |
Inverter output | |
Rated output apparent power | 10 kV·A. 15 kV·A. 20 kV·A. 30 kV·A. |
Nominal voltage | Three-phase 400 V a.c./ single-phase 230 V a.c. Guidance for specification option: 380, 400, 415 3F+N+PE (o 220, 230, 240 1F). Standard configurations with 3-3 distribution (multi IN/OUT settings available upon request). |
Voltage tolerance | +/-1%. |
Voltage waveform | Sinusoidal. |
Total harmonic distortion (THD) | < 1%. |
Nominal frequency | 50 or 60 Hz. |
Frequency tolerance | +/-2% (standard), +/-14% (extended). |
Overload capability | 120% continuous, 10 minutes at 135%, 60 seconds at 150%. |
Batteries | |
Location | Within UPS equipment enclosure. |
Type | Long life. |
Voltage | 12 V. |
Battery autonomy (stored energy time at rated power) | 60 minutes. |
Battery recharge time | |
To 80% capacity | 12 hours. |
Controls, indicators and alarms | |
Light emitting diode (LED) indication | Three-colored LED bar. Manufacturer guidanceGreen: Everything is OK on UPS. Load is protected. Orange: The load is supplied by UPS, but an alarm is active, a check is required. Red: The load is not supplied by UPS. Ongoing emergency. |
Communications and signalling | RS 232 serial ports, logic level port, floating contact ports, interface slot. |
Enclosure | |
Ingress protection (minimum) | IP20. |
Material and construction | |
Colour | Black. |
Noise emission | |
Sound pressure level in normal mode (maximum) | 58–62 dBA at 1 m. |
Properties | |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | |
Accessories | Not required. Output module 3.4 kV·A. Output module 5 kV·A. Output module 6.7 kV·A. Kit of 3 power module covers. Kit 4 drawers battery 9 Ah long life. Battery cabinets. Guidance for specification option: A range of battery cabinets are available. Refer to manufacturer's literature and insert requriements. Empty CPS cabinets. Guidance for specification option: A range of empty CPS cabinets are available. Refer to manufacturer's literature and insert requriements. |
Material | Other |