Verified by manufacturer 9 days ago
OS3 Control System (0 Zone)
The OS3 Control Panel provides reliable, user-friendly control for automated windows and ventilation systems, supporting BMS integration, sensors, and switches for precise environmental management.
Typical applications:
The OS3 Control Panel is a versatile and user-friendly control solution for automated window and ventilation systems. Designed to manage natural, environmental, and smoke ventilation, it allows precise, reliable operation of actuators and related devices.
The OS3 Control Panel supports seamless integration with Building Management Systems (BMS) for centralized control or can operate independently using connected switches and sensors. Its intuitive interface ensures easy configuration, monitoring, and operation, while robust construction guarantees reliable performance in commercial, educational, and public buildings.
Features and benefits:
Color | Grey |
Finish | Powder-coated |
Material | Steel |
Shape | Rectangle |
Length | 305 mm |
Width | 122 mm |
Height | 380 mm |
Warranty description | One year |
Uniclass | |
CAWS | S92/410 Control panels S92/410 Sprinkler alarm panels |
SKU Code | FCS13350000 |
Classification data | |
Enclosure | |
Ingress protection (minimum) | IP30. |
Material | Steel. |
Finish | Powder-coated. |
Colour | RAL 7035, grey. |
Nominal voltage | 230 V a.c. Guidance for specification option: +/-10%. From a 5 A unswitched spur. |
Nominal frequency | 50/ 60 Hz. Guidance for specification option: +/-10%. From a 5 A unswitched spur. |
Outputs | Mains output: 24 V. No mains: 18.5–28.8 V; 24.0 V (nominal). Guidance for specification option: Typical values. |
Batteries | |
Type | Sealed lead-acid batteries. Guidance for specification option: Sold separately. |
Voltage | 24 V (2 x 12 V). |
Battery autonomy (stored energy time at rated power) | 72 hours. |
Battery service life (minimum) | 3 years at 25ºC. |
Standard | To EN 12101-10. |
Dimensions | 380 x 305 x 122 mm. Manufacturer guidanceHeight x width x depth. |
Mass | 4.1 kg. Guidance for specification option: Approximate. |
Power consumption | Maximum 500 VA. |
MaximumCurrent | 7.0 A for 180 seconds. Guidance for specification option: Peak current can exceed 7.0 A for a short duration. |
Humidity | 10–90% (non-condensing). |
TemperatureRange | Storage temperature : -20 to +50°C. Operating temperature: -5 to +40 ºC. |
Clock | 10 years. Manufacturer guidanceReal time clock (RTC) battery life. |
Cable | Manufacturer guidanceTo ensure optimal performance and safety, please be advised that the maximum allowable cable length for the panel is 30 m for auxiliary connections (rain sensor, day-to-day switch). |
Accessories | Not required. Smoke detectors. OS3 Standard MCP. Guidance for specification option: Manual control point. OS3 Tamperproof MCP. Guidance for specification option: Manual control point. MCP dumb rest key. Guidance for specification option: FCS00200024. Activation key - open only. Guidance for specification option: FCS00200033. |
Technical characteristics, other | Overvoltage category: 2. Pollution degree: 2. |
Control system | 0 zones. Manufacturer guidanceNumber of zones. |
Country of product manufacture | United Kingdom |
Material | Steel |