NBS Source
I'm a manufacturer
Compare variants

NCA Series 100 - Curtain Type Fire Dampers

Verified by manufacturer 5 months ago

S100A*H - Square Spiggot, HEVAC Frame

HVC Supplies Variant:

CE marked fire damper, designed to impede the spread of fire and smoke and aid in overall fire safety.

Jump to:
+44 (0)1384 376555 Website

Application

  • Suitable for internal fire zone compartmentalisation.
  • Certified for use in masonry walls, drywall partitions and concrete floors.

Description

A CE marked fire damper, comprising a folding curtain type blade design. During normal conditions, the curtain type blade pack is recessed into the damper header and retained in place by a fusible link, leaving the duct open to airflow. Upon exposure to temperatures exceeding 72°C the fusible link will split, and the blade pack will be fully extended by springs to shut down the duct.


Series 100 fire dampers are designed to be used as part of building compartmentalisation, containing any potential fire within one zone and not allowing it to spread, thereby potentially savings lives, limiting damage to the building and making the job of fire fighters easier. Fire dampers allow an unrestricted flow of air during normal operation, but shutting down a potential transmission route in the event of fire.


Features and benefits:

  • CE marked curtain type fire damper.
  • Assessed against the requirements of BS EN 15650.
  • Four installation methods all with 120 minute ‘E’ ratings.
  • Galvanized steel construction as standard, stainless steel optional.
  • Vertical installations for masonry walls and drywall partitions.
  • Horizontal installation for concrete floor slabs.
  • Available to suit square, rectangular, circular and flat oval ducting.
  • Available with fixing lugs.

General information

Color

Grey

Guidance for specification option:

Galvanized or stainless steel.

Finish

Galvanized

Material

Steel

Brass

Stainless steel

Shape

Square

Circle

Oval

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/440 Dampers, fusible link type

U90/443 Dampers, fire/ smoke

U90/443 Dampers, fire and smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To BS EN 15650.

Test

To BS EN 1366-2.

Classification

To BS EN 13501-3.

Aerodynamic performance

To BS EN 1751.

Arrangement

Folding curtain blades in air stream.

Classification

E120.

Material

Galvanized steel.

Guidance for specification option:

Standard (fully galvanized steel).

Galvanized steel (case), Stainless steel (blades).

Guidance for specification option:

Optional.

Accessories

Not required.

Fixing lugs (FL).

Guidance for specification option:

Factory fitted fixing lugs (plate frame only).

Microswitch (MS).

Guidance for specification option:

Minimum height/ diameter restrictions apply.

Consult manufacturer for details.

Pull ring (PR).

Resettable link (RSL).

Electromagnet 24 V AC (EM24AC).

Guidance for specification option:

Minimum height/ diameter restrictions apply.

Consult manufacturer for details.

Electromagnet 24 V DC (EM24DC).

Guidance for specification option:

Minimum height/ diameter restrictions apply.

Consult manufacturer for details.

Electromagnet 230 V AC (EM230AC).

Guidance for specification option:

Minimum height/ diameter restrictions apply.

Consult manufacturer for details.

Electromagnet 230 V DC (EM230DC).

Guidance for specification option:

Minimum height/ diameter restrictions apply.

Consult manufacturer for details.

Fusible links

-

Fusing temperature

72°C.

Dimensions

Bespoke.

Guidance for specification option:

Insert requirements.

  • Spigot 6 mm under nominal (duct) width and height.
  • Recommended for sizes under 200 mm high.
  • Minimum size (width x height): 100 x 100 mm.
  • Maximum size (width x height): 1250 x 1000 mm.
  • Consult manufacturer's literature for details.

Connection

Square spigotted.

Manufacturer guidance

Duct connection.

Frame

HEVAC frame.

Manufacturer guidance

Frame type.

Steel grade

Not required.

Guidance for specification option:

Fully galvanized steel option.

430 grade stainless steel (SS430).

304 grade stainless steel (SS304).

316 grade stainless steel (SS316).

Guidance for specification option:

Marine spec.

Manufacturer guidance

Stainless steel grade (required if stainless steel material is selected).

Sustainability data

Country of product manufacture

United Kingdom

Similar products from HVC Supplies

NCA Series 400 - Single Blade Fire Dampers

NCA Series 400 - Single Blade Fire Dampers

NCA Series 700 - Multi Blade Fire Dampers

NCA Series 700 - Multi Blade Fire Dampers