Verified by manufacturer 3 months ago
KIWA BDA
Certificate type
WRAS
Certificate type
Twin plate heat interface units.
For domestic use. For instantaneous hot water and space heating production in communal and district heating systems. Suitable for utility rooms and kitchen cupboards.
Heat interface unit for indirect heating and instantaneous domestic hot water (DHW) with electronic PID control using Pressure Independent Control Valves (PICVs) with modulating actuators achieving a low primary return temperature as well as providing differential pressure control and flow rate regulation.
The heating circuit flow temperature is controlled by the modulation of the primary flow rate with the integrated PICV actuator, whilst the integrated pump modulates the secondary flow based on the design dT ensuring low secondary and primary return temperatures.
Weather compensation is applied to the set heating flow temperature using SmartTalk® two-way communication ensuring maximum system efficiency. Suitable for radiators, underfloor heating and fan coil units.
Domestic hot water is heated via a separate plate heat exchanger and the temperature is regulated by the modulation of primary flow rate with the integrated PICV actuator.
Features and benefits:
Color | White |
Finish | Powder-coated |
Material | Steel |
Shape | Rectangle |
Warranty description | Two year |
Uniclass | |
CAWS | T90/110 Heating system T90/110 Heating system |
Standard | Water Regulations Advisory Scheme (WRAS) Approved / CE Marked / BESA (British Engineering Services Association) UK Standard for Heat Interface Units. |
Casing | White powder coated steel. |
Insulation | Not required.Casing and pipework insulation required. |
Components | |
Controls | Pressure Independent Control Valve (PICV), electronic actuator and PID control. |
Model | Manufacturer guidanceConsult manufacturer and insert SKU code. |
Operating pressure (maximum) | 16 bar. |
Power supply | 220/240V, 50Hz. |
Maximum temperature | 85°C. |
Country of product manufacture | Romania |