NBS Source
I'm a manufacturer
Compare variants

ModuSat® Single Plate Double Circuit

Verified by manufacturer 3 months ago

SPDC-20

Evinox Energy Variant:

Single plate double circuit heating interface units.

Jump to:
+44 (0)1372 722277 Website

Application

Designed for installation with a suitable external DHW storage tank fed by the unit (not Evinox supply).

Description

The unit consists of a single plate heat exchanger, combined with electronic PID control using Pressure Independent Control Valve (PICV) with modulating actuator achieving a low primary return temperature as well as providing differential pressure control and flow rate regulation.


The SP-DC heat interface unit uses a diverter valve to switch secondary flow either through the heating circuit or fed to the external DHW tank and operates in DHW priority mode to provide fast recovery of hot water. In addition to this the ModuSat® can provide direct control of underfloor heating output temperature without the need for any underfloor pumps, blending valves or mixing valves.


Available in a range of plate sizes and connection configurations, the unit is suitable for many different type of installation.


The heating circuit consists of a plate heat exchanger (PHE), safety relief valve, pressure gauge, flow and return temperature sensors, Wilo PWM circulation pump and expansion vessel. The heating circuit flow temperature is controlled by the modulation of the primary flow rate with the integrated PICV actuator. Weather compensation is applied to the set heating temperature using SmartTalk® two-way communication. Suitable for radiators, underfloor heating or fan coil units.


Features and benefits:

  • Pipe and case insulation (optional).
  • Pipework constructed from copper.
  • External filling loop (optional).
  • SmartTalk two-way communication.
  • Remote monitoring, alarms, and diagnostics.
  • Wilo PWM Pump – Provides compliance with EU ErP Directive 2015.
  • Includes inbuilt TCP/IP technology to operate on an Ethernet network if required.
  • Capable of reading an electricity meter (option for ENE3).
  • Flushing bypass kit enables the primary side of the system to be flushed and cleaned without damage to the unit.

General information

Color

White

Shape

Rectangle

Width

467 mm

Height

800 mm

Uniclass

Pr_60_60_38_36 Heat interface unitsPrimary

CAWS

T90/110 Heating system

T90/110 Heating system

Specification data - Heat interface units

Standard

Water Regulations Advisory Scheme (WRAS) Approved.

Duty

-

Primary flow temperature

70-80°C.

Primary return temperature

37.7°C.

Flow rate

0.057-0.074 kg/s.

Insulation

Not required.

Casing and pipework insulation required.

Components

-

Primary

Space heating heat exchanger.

Secondary

Diverter valve.

Controls

Pressure Independent Control Valve (PICV), electronic actuator and PID control.

Power supply

220/240V, 50Hz.

Maximum temperature

95°C.

Capillary Brazing

Copper.

Optional items

Not required.

External filling loop.

Literature

ModuSat® Single Plate Double Circuit Data Sheet

ModuSat® Single Plate Double Circuit Data Sheet

Similar products from Evinox Energy

ModuSat XR-ECO Combined Heating, Domestic Hot Water and Cooling

ModuSat XR-ECO Combined Heating, Domestic Hot Water and Cooling

ModuSat® Floor Standing HIU With Integrated Tank

ModuSat® Floor Standing HIU With Integrated Tank

ModuSat® XR Single Plate Cooling

ModuSat® XR Single Plate Cooling

ModuSat® XR Single Plate Heating

ModuSat® XR Single Plate Heating

ModuSat® XR-ECO Single Plate Domestic Hot Water

ModuSat® XR-ECO Single Plate Domestic Hot Water

ModuSat® XR-ECO Twin Plate

ModuSat® XR-ECO Twin Plate