Color | White |
Finish | Smooth |
Material | Other Guidance for specification option: Thermoplastic; consult manufacturer for details. |
Shape | Rectangle |
Uniclass | |
CAWS | V90/319 Cable distribution cabinets V90/320 Distribution boards |
Standards | To EN IEC 60898-1 and EN IEC 60947-2. |
Rated current (InA) | Not applicable. |
Rated operational voltage (Ue) | To EN IEC 60898-1, 230 V a.c./ 220 V d.c. |
Rated impulse withstand voltage (Uimp) | Not applicable. |
Rated frequency | 50 Hz.60 Hz. |
Number of poles | One. |
Rated short circuit capacity (Icn) | To EN IEC 60898-1, ≤25 A: 25 kA. |
Tripping characteristic | Type B.Guidance for specification option: Reference temperature for tripping characteristics, to EN IEC 60947-2: 55°C. Type C.Guidance for specification option: Reference temperature for tripping characteristics, to EN IEC 60947-2: 55°C. Type D.Type K.Guidance for specification option: Reference temperature for tripping characteristics, to EN IEC 60947-2: 20°C. Type Z.Guidance for specification option: Reference temperature for tripping characteristics, to EN IEC 60947-2: 20°C. Manufacturer guidanceReference temperature for tripping characteristics, to EN IEC 60898-1: 30°C. |
Mounting method | DIN rail. |
Accessories | Guidance for specification option: Consult manufacturer for options and insert requirements, or omit. |
Rated insulation voltage | According to EN IEC 60664-1, 250 V a.c. (phase to ground); 500 V a.c. (phase to phase). |
Operating voltage | To EN IEC 60947-2 (minimum), 12 V a.c./ 12 V d.c. |
Technical characteristics, other | Pollution degree: 2. Manufacturer guidanceElectrical endurance to EN IEC 60947-2:
|
Breaking capacity | Rated ultimate short-circuit breaking capacity (Icu), to EN IEC 60947-2: ≤25 A: 25 kA; ≥32 A: 15 kA. |
Material | Other Guidance for specification option: Thermoplastic; consult manufacturer for details. |