NBS Source
I'm a manufacturer

HFP Plant Control Module with SCI

Verified by manufacturer 3 months ago

Hochiki Europe (UK) Ltd Third party certifications:
  • ISO 9001 Quality Management

    Certificate type

  • Certificate of Approval

    Certificate of Approval

    Certificate type

A loop powered input/output module with four independent change-over relay outputs and four monitored inputs.

Jump to:
+44 (0)1634 266566 Website

Application

Fire detection systems:


  • Schools & Universities
  • Multiple Occupancy Accommodation
  • Hospitals / Care Homes
  • Office Buildings
  • Airports
  • Rail / Tube Stations
  • Hotels / Pubs & Hospitality
  • Retail / Supermarkets
  • Factory / manufacturing plants
  • Hazardous Areas
  • Off-shore

Description

The CHQ-PCM(HFP)-SCI is a loop powered input/ output module with four independent change-over relay outputs and four monitored inputs. The outputs feature N/O and N/C volt free contacts and can be driven separately under the control of the fire alarm panel, to be used for the control of devices such as dampers or for plant and equipment shutdown. The four inputs are provided for local fire and fault monitoring and these are fully monitored for

open and short circuit, which if required, can be enabled or disabled in pairs using a two-way DIL switch.


Note: The state of the relay contacts will be indeterminate until the unit is powered. A back box is also available (CHQ-BACKBOX) which, when used in conjunction with the CHQ-PCM(HFP)-SCI, increases the IP rating to IP65. When using heavy cables we recommend the use of the SMB-1 Module Enclosure in conjunction with the SMB-ADAPTOR plate. The unit is also available in a DIN Rail mountable enclosure – CHQ-PCM/DIN(SCI).


Features and benefits:

  • Loop powered with single loop address.
  • Provides four change-over relay outputs, four independent inputs for monitoring of volt free contacts.
  • Each input can be configured to monitor either Normally Open or Normally Closed contacts.
  • Also available as DIN.
  • Both models feature an integral SCI.
  • Deeper, glanded IP65 backbox available.
  • Can be used with CHQ-BACKBOX to comply with BS 7671.
  • Approved by LPCB.
  • SIL2 and Railway Approved variants available.
  • Quiescent current (typical) 330 μA.
  • Current consumption (whilst polling) 22 mA ± 20 %.
  • Relay contact rating 30 V d.c., maximum, 1 A (resistive load).
  • Input EOL resistor 10 K Ω, ±5%, 0.25 W.
  • Input threshold level ON=470 Ω, Short cct <50 Ω, Open cct >100 KΩ.
  • Maximum rated current 1 A (switch closed).
  • Leakage current 3 mA (switch open).

General information

Color

White

Finish

Gloss

Material

Plastic

Shape

Rectangle

Length

157 mm

Manufacturer guidance

DIN Module L108 x W119 x D24 mm.

Width

127 mm

Height

35 mm

Warranty description

Three year

Uniclass

Pr_75_80_30_72 Relay interface modulesPrimary

CAWS

W90/125 Fire detection and alarm systems in non-domestic premises

Specification data - Relay interface modules

Standards

To EN 54-17 and EN 54-18.

Third-party approval

Approved by LPCB.

Mounting

As Standard.

DIN Rail version.

Voltage

17–41 V d.c.

Communications

Digital communication using ESP.

Sustainability data

Contains Red List materials

No

Country of material origin

China

Country of product manufacture

United Kingdom

Material

Plastic

Manufacturing plant location

Expected Life

Ten year

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

ISO 9001 Quality Management

ISO 9001 Quality Management

Certificate of Management System Registration - ISO 9001:2015 - Quality Management Systems

Certificate of Approval

Certificate of Approval

Certificate of Product Approval - EN 54-17 and EN54-18 | Products: CHQ SCI Range

Literature

CHQ-PCM(HFP)-SCI Analogue Plant Control Module

CHQ-PCM(HFP)-SCI Analogue Plant Control Module

Hochiki BS 5839 Guide

Hochiki BS 5839 Guide

Hochiki Corporate Overview

Hochiki Corporate Overview

Hochiki - ESP - Intelligent Fire Detection - Range Overview

Hochiki - ESP - Intelligent Fire Detection - Range Overview

Hochiki Project Portfolio

Hochiki Project Portfolio

Case studies

BiG Shopping Mall (Retail - ESP)

BiG Shopping Mall (Retail - ESP)

Cantina Monte Rossa (Industrial - ESP)

Cantina Monte Rossa (Industrial - ESP)

Dubai Metro (Transport - ESP)

Dubai Metro (Transport - ESP)

Kervo Fruit Processing (Industrial - Latitude and ESP Intelligent)

Kervo Fruit Processing (Industrial - Latitude and ESP Intelligent)

Livingstone Academy (Education - ESP Intelligent)

Livingstone Academy (Education - ESP Intelligent)

Sacro Cuore Don Calabria Hospital (Healthcare - Latitude & ESP)

Sacro Cuore Don Calabria Hospital (Healthcare - Latitude & ESP)

Technical Metals (Industrial - ESP)

Technical Metals (Industrial - ESP)

St Pancras International (Transport - ESP)

St Pancras International (Transport - ESP)

Titanic Distillers (Industrial - ESP)

Titanic Distillers (Industrial - ESP)