You are viewing content for United Kingdom.
Choose a country to see content for your location. Changing region will navigate you to the homepage.
Verified by manufacturer 2 months ago
A greywater recycling system.
The Aquacell G Series can be incorporated into residential apartment buildings, commercial office towers and more.
The Aquacell G Series provides a simple modular solution for on site greywater recycling. The system features a controlled, robust and comprehensive treatment process that combines physical, microbiological and oxidative treatments in one efficient package.
The treated greywater can then be reused for non-drinking applications such as toilet flushing, cooling towers, irrigation and more.
Greywater can come from our showers, baths, basins and washing machines. It may be contaminated with a range of soluble and insoluble (particulate) substances like soaps, detergents, skin, saliva, dirt and lint. Each type of contaminant must be treated appropriately, whether it is detergent/surfactant, organic, microbial or particulate. Aquacell G Series has been designed with a multi-barrier approach and combines a range of purifying processes to remove all contaminants, making the greywater ready to use again.
Features and benefits:
Finish | Other |
Material | Other |
Shape | Other |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | Other |
Uniclass | |
CAWS | S90/160 Rainwater/ grey water recycling system S17/110 Grey water reclamation system |
SKU Code | G Series |
Classification data | |
Standards | To BS 12056-2:2000, BS 8525-1:2010 and BS 8558:2015. |
Performance characteristics | |
Fluid | |
Sources | Above ground wastewater drainage system with internal stacks (supplied by others). |
End uses | Non-potable applications, including toilet flushing, cooling towers, irrigation and more. |
Peak treatment capacity (flowrate) | Manufacturer guidanceConsult manufacturer and insert requirements. |
Storage volume (maximum) | Manufacturer guidanceConsult manufacturer and insert requirements. |
Storage period (maximum) | Manufacturer guidanceConsult manufacturer and insert requirements. |
Monitoring and controls | |
General | Remote monitoring and data acquisition system. Guidance for specification option: The plant monitors the following parameters and uses controls to ensure reliable and safe recycled water supply is available at all times:
Manufacturer guidanceTo monitor all process variables and critical control points. Includes ethernet-based human interface with real-time remote operation and control via web-connected PC, trending and alarming function systems via email. |
Visual indicators | Touch screen on the face of the panel provides a visible display of plant status, motor manual/off/auto, critical control point status. Manufacturer guidanceA touch screen on the face of the panel provides a visible display of plant status, motor manual/off/auto, critical control point status. The plant operates via the touchscreen interface without remote operation in the event of communications failure. |
Control functions | Motor control centre and programmable automation controller. |
Product characteristics | |
Tanks | Manufacturer's choice. Guidance for specification option: Pump station and greywater buffer tank. Manufacturer guidanceUntreated greywater will gravitate along the dedicated collection network to a pump station which will be located on the basement level, from here it will then be pumped on demand into a buffer tank. |
Tank ancillaries | Back flow prevention: supplied by others. |
Biological treatment | Aerobic biological treatment. Manufacturer guidanceAir is diffused into the wastewater to create aerobic conditions where a biomass will grow in both aerobic and anoxic zones. |
Disinfection | Ultraviolet (UV) disinfection. Guidance for specification option: Ultraviolet (UV) radiation system to US EPA standards with UVI and UVT monitor and chlorination system. Manufacturer guidanceAlarms in the UV system (lamp needing clean, lamp deterioration, lamp end of life, reduced UV transmissivity) are detected by the photo intensity monitor, which transmits information to the remote monitoring system. This ensures appropriate UV dose at all times. |
Chemical treatment | Manufacturer's choice. |
Equipment skids | 1.4307 Grade (304L) stainless steel. |
Pipes | Collection and distribution pipelines: Supplied by others. |
Collection tank | Pump station and greywater buffer tank. Manufacturer guidanceUntreated greywater will gravitate along the dedicated collection network to a pump station which will be located on the basement level, from here it will then be pumped on demand into a buffer tank. |
Storage | Treated water storage tank. |
Pump | Submersible pumps. Guidance for specification option: Pumps within the buffer tank will transfer screened wastewater to the Aquacell greywater treatment system. |
Filter | Buffer tank: Screen filter. Guidance for specification option: Course filter. The pump station will feed the buffer tank via a screen to remove non-biodegradable solids from the influent. Membrane tank: Hollow-fibre ultrafiltration membrane with pulse air scour clean-in-place system. Guidance for specification option: Fine filter.
|
Ventilation | Vent to stack (supplied by others). Odour control mechanical ventilation (supplied by others). |
Identification | Pipework: Colour-coded and labelled to BS 1710.Recycled water meter and tap handles: Coloured and/ or appropriately labelled. Manufacturer guidance
|
Testing | Testing and setting to work: Commissioning of the plant to CIBSE standards. Performance testing of the plant via laboratory analysis in accordance with issued approval. Documentation: Operation and maintenance manual. Servicing and maintenance: Undertake for 12 months after completion. Manufacturer guidanceThe operation and maintenance manual includes as a minimum:
|
Contains Red List materials | Yes |
Country of material origin | Australia |
Country of product manufacture | Australia |
Material | Other |
Recyclability | Manufacturer guidanceMajor items including stainless steel, LDPE, HDPE etc. can be recycled at end-of-life. Some components are unable to be recycled at the end-of-life. The percentages vary depending on system sizes and design requirements. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | Manufacturer guidance>20% |
Expected Life | 25 year |