Verified by manufacturer today
Safe and reliable fire shutters, fully tested and certified in accordance with the latest fire standards BS EN 1634-1:2014 + A1:2018 and BS EN 16034:2014.
Our roller shutters are used in a variety of internal industrial and commercial facilities including:
Safe and reliable fire shutters, fully tested and certified in accordance with the latest fire standards BS EN 1634-1:2014 + A1:2018 and BS EN 16034:2014.
Test report: Warrington Fire WF Report No. 410300 dated of 27th June 2019 in accordance with BS EN 1634-1 2014+ A1 2018.
Features and benefits:
Components:
Color | Silver Other |
Finish | Galvanized Powder-coated |
Material | Steel |
Shape | Rectangle Square |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L20/60 Doors L20/610 Roller shutters/ curtains |
Classification data | |
Standard | To BS EN 1634-1:2014 + A1:2018 and BS EN 16034:2014. Manufacturer guidanceTest report: Warrington Fire WF Report No. 410300 dated of 27th June 2019 in accordance with BS EN 1634-1 2014+ A1 2018. |
Opening sizes | Guidance for specification option: Consult manufacturer for options and insert requirements. |
Format | Internal. |
Arrangement | Vertical, face-fitted across opening. |
Performance | |
Fire performance | |
Fire resistance | One hour fire rating. Two hour fire rating. Four hour fire rating. |
Watertightness | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. |
Resistance to wind load | To BS EN 12424, up to Class 3. |
Acoustic performance | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. |
Thermal resistance | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. |
Air permeability | Manufacturer's standard. Guidance for specification option: Consult manufacturer for details. |
Frame and guides | |
Material | Steel. Guidance for specification option: Bottom rail:
Side guides and angles:
Roller barrel:
Endplates:
Coil casings:
|
Finish | Galvanized. Guidance for specification option: Side guides and supporting angles are galvanized as standard. Powder-coating. Guidance for specification option: Note that additional cost applies, consult manufacturer for details. |
Colour | Galvanized. Other. Guidance for specification option: Insert colour requirements, RAL or BS. Note that additional cost applies, consult manufacturer for details. |
Film thickness (minimum) | Manufacturer's standard (where applicable). |
Installation fasteners | Guidance for specification option: Insert requirements to suit structure. |
Frame accessories | Guidance for specification option: Consult manufacturer for options and insert requirements, or omit. |
Shutter curtain | |
Lath material | Galvanized steel. Guidance for specification option:
|
Profile | Concave, plain, 76 mm. |
Finish and colour | Galvanized. Powder-coating. Guidance for specification option: Insert colour requirements, RAL or BS. Note that additional cost applies, consult manufacturer for details. |
Weight | 45 kg/m². |
Mode | Automatic, electric 240 V single-phase motor, geared drive. Automatic, electric 415 V three-phase motor, geared drive. Manufacturer guidance
Consult manufacturer for power requirements. |
Control | Push button station. Guidance for specification option: “UP”, “DOWN” and “STOP” buttons. |
Accessories | None. Audio visual warning panel. Guidance for specification option: Provides a warning that the fire shutter is about to close automatically via the fire alarm system. The panel requires a 240 V supply together with an appropriate signal from the fire alarm system. The panel also includes a battery backup system and an adjustable timer close facility. |
Material | Steel |