NBS Source
I'm a manufacturer

FirePro® High Strength Compound - Fire penetration seal

Verified by manufacturer 3 months ago

ROCKWOOL Ltd

High strength compound for reinstating the fire performance of floor and wall constructions.

Jump to:
BOS
+44 (0)1656 862621 Website

Application

  • Re-instating the fire resistance of wall and floor constructions.
  • Load bearing floors.
  • Wall penetrations.
  • Load bearing seals around unsupported fire dampers.

Description

HS Firestop Compound is a specially formulated gypsum-based mortar, which is mixed with water to create a workable range from stiff to pourable mix. HS Firestop Compound is also suitable for pre-casting into convenient size blocks for use in wall openings. Services passing through the High Strength Compound should be treated with a tested fire stopping solution suitable for the specific application.


Features and benefits:

  • Unsupported spans of up to 1800 mm.
  • Suitable for use with multiple service penetrations.
  • Can be formed into blocks.
  • Good acoustic barrier.
  • High load-bearing capacity.
  • Effective smoke seal.
  • Rapid setting.

General information

Color

Grey

Finish

Trowelled

Material

Gypsum

Shape

Formless

Length

Bespoke

Manufacturer guidance

Supplied in 20kg bags

Width

Bespoke

Manufacturer guidance

Supplied in 20kg bags

Height

Bespoke

Manufacturer guidance

Supplied in 20kg bags

Uniclass

Pr_20_31_53_43 Intumescent mortarsPrimary

CAWS

P12/340 Intumescent mortar

P12/37 Intumescent mortar

P12/342 Fire-resisting mortar

Specification data - Intumescent mortars

Material

Gypsum based.

Fire resistance

To EN 1366-3, up to four hours/ EI120.

Density

1750–1900 kg/m³.

LoadBearing

false

Acoustic performance

Rw 57 dB.

Guidance for specification option:

100 mm depth.

Maximum unsupported span

1800 mm.

ThermalConductivity

0.45 W/mK.

Setting expansion

0.1%.

Typical yield

±6 bags/m² at 100 mm depth.

Weight

20 kg.

Sustainability data

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Similar products from ROCKWOOL Ltd

FirePro® Firestop Compound - Fire penetration seal

FirePro® Firestop Compound - Fire penetration seal