Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Verified by manufacturer 1 month ago

Coopers Fire Ltd Third party certifications:
  • KIWA BDA

    KIWA BDA

    Certificate type

  • Constructionline Gold

    Constructionline Gold

    Certificate type

  • IFCC

    IFCC

    Certificate type

Active fire curtain barrier assemblies.

Jump to:
BOS
+44 (0)23 9245 4405 Website

Application

  • Suitable to be used to form a virtually continuous barrier as a fire separating element.
  • Suitable for use as protected means of escape, lobbies and receptions, opening in walls, egress and corridor separations, boundary protection, stairs and escalators, lifts and lift lobbies.

Description

An electrically operated active fire curtain barrier assembly. Active fire curtain barrier assemblies comprises a woven steel and glass fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.


The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position. Has been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). Has been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (180 minutes integrity). Has been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (90 minutes).


Operation:

Active fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.


Fire resistance:

180 minutes (3 hours) integrity.


Period of radiation:

107 minutes <15 kW/m².


Classification:

E180 EW90 C0 (single).


Product certification, performance and/ or testing:

  • Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Complete barrier assemblies have been tested for fire resistance to BS EN 1634-1, as required by BS 8524-1. The barrier assembly achieved 180 minutes integrity and 90 minutes radiation.
  • Complete barrier assemblies have been tested for impact to BS 5234-2 as required by BS 8524-1.
  • Complete barrier assemblies have been tested for reliability, durability and self-closing to BS EN 14600 as required by BS 8524-1.
  • Complete barrier assemblies have been tested for gravity fail-safe as required by BS 8524-1.
  • Motor(s) used within barrier assemblies in the above tests have been tested for operation at temperatures of 400°C as required by BS 8524-1.
  • Complete barrier assemblies have been tested for smoke leakage to BS EN 1634-3 as required by BS 8524-1.
  • The fabric used within active fire curtain barrier assemblies have been tested to BS EN 1634-3.
  • The fabric used within active fire curtain barrier assemblies have been tested to BS 476 pt 6 and pt 7.


Approving standards:

The following standards apply to this product:

  • BS 8524-1:2013, Specification for active fire curtain barrier assemblies.
  • BS EN 1634-1:2014, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows.
  • BS EN 1634-3:2004, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies.
  • BS EN 1363-1:1999, Fire resistance tests – Part 1: General requirements.
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures.
  • BS EN 13501-2:2007+A1, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating.
  • BS EN 14600:2005, Doorsets and openable windows with fire resisting and/ or smoke control characteristics. Requirements and classification.
  • BS 476-6:1989+A1:2009. Fire tests on building materials and structures. Method of test for fire propagation for products.
  • BS 476-7:1997. Fire tests on building materials and structures. Method of test to determine the classification of the surface spread of flame of products.
  • BS EN ISO 14184-1:2011. Textiles. Determination of formaldehyde. Free and hydrolysed formaldehyde (water extraction method).
  • BS EN ISO 9001:2008, Quality management system.
  • BS EN ISO 14001:2004, Environmental management system.

General information

Color

Other

Finish

Galvanized

Material

Steel

Fabric

Guidance for specification option:

Glass fabric.

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

BS 8524‑1, BS EN 1634‑1, BS EN 1634‑3, BS EN 1363‑1, BS EN 1363‑2, BS EN 13501‑2 +A1, BS EN 14600, BS 476‑6:1989+A1, BS 476‑7, BS EN ISO 14184‑1, BS 6323‑5:1982, BS EN ISO 9001:2008, BS EN ISO 14001:2004, ISO Guide 65, BS EN ISO 17065, BS EN 1634‑3, BS 8524‑1, BS 5234‑2, BS EN 14600.

Barrier assemblies

To BS 8524-1.

Test standards

Vertical, horizontal and angled to BS EN 1634-1.

Third-party certification

Certified by IFCC Ltd.

Size

Bespoke.

Guidance for specification option:

Insert requirement.

Performance

-

Pressure and impact

Guidance for specification option:

As per BS 8524, impact and pressure tested as large soft body impact and crowd pressure in accordance with BS 5234-2.

Durability class

C1.

Guidance for specification option:

C1 - 500 cycles tested, as per BS 8524 Annex D, "Durability of self-closing".

Smoke containment

Not required.

Required.

Guidance for specification option:

Option available under BS EN 1634-3.

Fire resistance

E180 Integrity; EW90 Radiation.

Reaction to fire

Guidance for specification option:

Fabric used in the construction of a barrier assembly shall be tested in accordance with BS 476-6 and BS 476-7 to achieve a Class 0 or Class 1 rating, or BS EN ISO 1716 or BS EN ISO 1182 and BS EN 13823 to achieve a minimum of B-s3,d2 (Class 0 equivalent) or a minimum of C-s3,d2 (Class 1 equivalent).

Barrier units

Single.

Overlapped.

Multiple.

Vertical.

Manufacturer guidance

Flexible metallic fabric.

  • Fabric type is EFP™ 2/1000/DGI a glass fibre, stainless steel wire reinforced, fabric coated with an intumescent graphite silicone elastomer 1900 g/m² –5% +10%.
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance).
  • The fabric material passed testing for fire propagation to BS 476-6+A1, and for surface spread of flame to BS 476-7 to achieve National Class ‘0’.
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).

Deployment

Full.

Fire alarm system active.

Local detector active.

Thermal activation.

Delayed.

Partial deploy.

Controlled decent.

Gravity fail safe deployment.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Beam protection and obstruction warning.

Guidance for specification option:

Will sound in the event of an obstruction being placed at the barrier drop line.

Emergency retract.

Guidance for specification option:

Touch-button retract facility for multi-escape.

Split drop delay.

Guidance for specification option:

Will partially deploy to pre-determined level to permit escape.

Visual alert system.

Guidance for specification option:

Light warning system.

Voice warning.

Guidance for specification option:

Auto-spoken multi-message facility.

Emergency egress buttons.

Emergency access buttons.

Obstruction warning system.

Audible visual warning systems.

Remote test switches.

Heat and smoke detectors.

Building management system.

Split drop delay.

Classification

E180 EW90 C1, BS 8524.

Frame colour/ finish

Galvanized Steel.

Steel.

Polyester powder-coated, RAL 9017.

Polyester powder-coated, RAL 9010.

Polyester powder-coated, RAL.

Guidance for specification option:

Insert requirement.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

285 kg CO₂ eq/kg

Self declared

Manufacturer guidance

285.92 tCO2e for yearly emissions

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
IFC
-

1

Revit

Revit 2017

1

Third party certifications

KIWA BDA

KIWA BDA

CERTIFICATED INSTALLER OF ACTIVE FIRE PROTECTION

Constructionline Gold

Constructionline Gold

CERTIFICATE OF MEMBERSHIP

IFCC

IFCC

IFC FireMaster Plus

Literature

FireMaster® Plus² Active Fire Curtain Barrier

FireMaster® Plus² Active Fire Curtain Barrier

Case studies

Blavatnik School of Government, University of Oxford. Bespoke Fire Curtains and Smoke Curtains

Blavatnik School of Government, University of Oxford. Bespoke Fire Curtains and Smoke Curtains

Harris Calnan Construction Company (HCCC) - FireMaster Fire Curtains

Harris Calnan Construction Company (HCCC) - FireMaster Fire Curtains

HOTEL RUSSELL, LONDON, UK

HOTEL RUSSELL, LONDON, UK

The SSE Hydro, Glasgow. Fire Curtains and Smoke Curtains

The SSE Hydro, Glasgow. Fire Curtains and Smoke Curtains

Similar products from Coopers Fire Ltd

Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain.  - Fire Curtain Vision Panel

Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel

Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina

Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina

Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain