Verified by manufacturer 5 months ago
Warrington Fire
Certificate type
Active fire curtain barrier assemblies that close from each end of a void to meet and shut in the middle.
Suitable for use in applications which require an active fire curtain barrier that close from each end of a void to meet and shut in the middle.
The barrier assemblies comprise a fire-resistant fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick mild steel box. The edges of the curtain are retained inside side guides, providing pressure resistance of at least 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.
The barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.1 m/s). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 + A1:2018 for ‘Fire Resistance’ (120 minutes' integrity). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 + A1:2018 for ‘Fire Resistance’ (120 minutes integrity).
Operation:
Barrier assemblies commence movement upon initiation of BMS alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.
In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.
Fire resistance:
120 minutes' (2 hours') integrity.
Radiation resistance:
15 minutes.
Product certification, performance and/ or testing:
Approving standards:
The following standards apply to this product:
Color | Other |
Finish | Galvanized Powder-coated |
Material | Fabric |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: From date of commissioning. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | |
Barrier assemblies | To BS EN 8524-1. |
Test standards | Compliant to BS EN 1634-1:2014 +A1:2018. |
Size | Guidance for specification option: Insert requirement. Consult manufacturer for details. Power supply size: 600 x 600 x 210 mm (w x h x d). |
Performance | |
Pressure and impact | SD. |
Durability class | C1. |
Smoke containment | Not available. |
Fire resistance | 120 minutes (2 hours) integrity. |
Barrier units | Flexible metallic fabric.Guidance for specification option:
|
Deployment | Full. |
Activation | Commences movement upon initiation of alarm or power or system failure. |
Accessories | None.Visual alert system.Guidance for specification option: Light warning system when mains or emergency power is available. Voice warning.Guidance for specification option: Audio or spoken multi message facility when mains or emergency power is available. |
Frame colour/ finish | Galvanized steel. Powder coated. Guidance for specification option: Available upon request, insert colour requirements. |
Type | Face fixed. Reveal fixed. |
Fixing | Face fixed. Top fixed. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | Coopers Fire offer a take back service where product is broken down into component parts. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |