Single Unit - SI-N Housing - E60
The FireCurtain FM1 is an automatic fire curtain which seals off an area to contain a fire and to prevent that fire from spreading to other areas.
Suitable for use in fire barrier applications.
The FireCurtain FM1 is an automatic fire curtain which seals off an area to contain a fire and to prevent that fire from spreading to other areas. The automatic fire curtain has been tested according to multiple standards and also has a CE mark. The specially developed unwinding mechanism is built into the roller and it unrolls in a gravity fail safe manner without needing power.
Features and benefits:
Dimensions:
The compact modular system is available in the following dimensions:
Drive technology:
The safe operation of an automatic fire curtain is assured: the unwinding mechanisms have different performance classes for all operating modes.
The unwinding mechanism is installed within the roller and contains, in addition to the high-quality DC motor with its planetary gears, a control board with its own intelligence for carrying out the essential safety-related functions:
Classifications:
In accordance with EN 16034 and 13241:
Compliance:
Color | Other |
Finish | Powder-coated |
Material | Glass Fibre Fabric Polyurethane Steel |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Classification data | |
Standards | |
Barrier assemblies | To BS 8524-1. |
Test standards | Vertical, horizontal and angled to BS EN 1634-1. |
Third-party certification | CE certified. |
Size | 4000 x 3750 mm. Manufacturer guidanceLength x height maximum. |
Performance | |
Durability class | C2. |
Fire resistance | To EN 13501-2, E 60. |
Reaction to fire | To EN 13501-1, A2-s1,d0. |
Barrier units | Single, SI-N. |
Deployment | Full. |
Activation | SKC-SC control panel. Guidance for specification option: The SKC-SC control panel is designed for safe operation of the fire curtain and complies with ISO 21927-9 and BS 8524. There is a power supply which guarantees that the control functions are maintained for at least 72 hours according to the EN 12101-10 standard. |
Accessories | Hold-open device. Guidance for specification option: Control of the fire curtain is via a hold-open system according to EN 14637 and the DIBt Guideline. Autonomous controls for initiating the closing process via the connected smoke detectors or manual control units. Alarm saving when released. |
Bottom bar | Type UK. Type U. Type ID. |
Material | Glass Fibre Fabric Polyurethane Steel |