FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper

Verified by manufacturer 15 days ago

Design .01 Manual and thermal

Mandik UK Limited Variant:
Third party certifications:
  • Type Examination Certificate

    Certificate type

  • Hygiene requirements to VDI 6022

    Certificate type

  • Certificate of Conformity

    Certificate type

  • DoP

    DoP

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

  • Certificate of constancy of performance

    Certificate type

  • EPD

    EPD

    Certificate type

A single blade fire damper for HVAC ductwork.

Jump to:
0117 4526376 Website

Application

Fire dampers are suitable for installation in vertical and horizontal passages of fire-separating constructions. The fire damper can be installed into:

  • Solid wall construction made of, e.g. normal concrete/ masonry, porous concrete with a minimum thickness 100 mm.
  • Gypsum wall construction with minimum thickness 100 mm.
  • Solid ceiling construction made of, e.g. normal concrete or porous concrete, with minimum thickness according to BS EN 1366-2.
  • Outside the wall construction (solid and flexible).

Additional applications may be available, please reference product Technical Specifications for more detail.

Description

A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors.

Features and benefits:

  • Dampers from 100 x 100 mm to 1000 x 500 mm.
  • CE certified to BS EN 15650.
  • Tested in accordance with BS EN 1366-2.
  • Classified to BS EN 13501-3.
  • Fire resistance up to EI 120 S.
  • Damper actuating: mechanical or electrical.
  • Can be used in explosion-hazard environments.

General information

Color

Silver

Finish

Galvanized

Material

Steel

Calcium silicate

Shape

Rectangle

Square

Length

375 mm

Width

100 mm

110 mm

125 mm

140 mm

150 mm

Show more

Height

100 mm

110 mm

125 mm

140 mm

150 mm

Show more

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To BS EN 15650.

Test

To BS EN 1366-2.

Classification

To BS EN 13501-3.

Aerodynamic performance

To BS EN 1751.

Guidance for specification option:

Damper body, for size: A<160 or B<160 Class B; A≥160 or B≥160 Class C.

Damper blade: Class 2.

Arrangement

Single-blade.

Classification

EIS30.

EIS45.

EIS60.

EIS90.

EIS120.

Manufacturer guidance

Refer to the manufacturer's literature for placement and installation details to achieve the required fire resistance values.

Material

Zinc-coated steel.

Fusible links

-

Fusing temperature

72°C.

Guidance for specification option:

As standard.

104°C.

147°C.

Spare fusible links

-

Manufacturer guidance

Insert requirements or omit.

Dimensions

-

Manufacturer guidance

Consult manufacturer's literature for performance details and insert requirements.

  • Damper body: From 100 x 100 mm to 1000 x 500 mm.
  • The dampers are available in any 5 mm increment within their minimum and maximum sizes.
  • Construction length: 375 mm or 500 mm.

Actuator

Mandik.

Control module

Not required.

Communication and control module MDCM.

Manufacturer guidance

The MDCM damper control module is connected on a bi-directional communication loop back to a control panel, typically located at the FCC. This accessory is only required with MANDIK control systems.

Cladding

Not required.

Protective cladding boards.

Manufacturer guidance

Protective cladding boards must be used as part of the

penetration filling of installation with ablative coated batt.

Boards are made of PROMATECT-H, thickness 10 or 15 mm

according to the damper size (SUPALUX, thickness 9 or 15

mm can be used as an alternative).

Frame

Not required.

Reinforcing frame VRM2-B.

Manufacturer guidance

If the damper is installed outside the fire separation

construction with insulation from ISOVER and fire

resistance is ≥ EI 90 S, VRM2-B reinforcement frame must

be used.

Duct connection

Mandik FFDM breakaway joint.

Guidance for specification option:

FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained.

Refer to FFDM – Technical specifications for options and insert requirements.

Breakaway joint (supplied by others).

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Breakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper.

Sustainability data

Material

Steel

Calcium silicate

Third party certifications

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

Type Examination Certificate

Type Examination Certificate

Certificate ATEX

Hygiene requirements to VDI 6022

Hygiene requirements to VDI 6022

Hygienic assessment - Fire dampers

Certificate of Conformity

Certificate of Conformity

Declaration of conformity ATEX

DoP

DoP

FDMB – Declaration of performance (UKCA)

DoP

DoP

FDMB – Declaration of performance (CE)

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

FDMB – Certificate (UKCA)

Certificate of constancy of performance

Certificate of constancy of performance

FDMB – Certificate (CE)

EPD

EPD

Environmental Product Declaration - Fire Dampers

Literature

FDMB – Technical specifications (164/22)

FDMB – Technical specifications (164/22)

Appendix ATEX

Appendix ATEX

FDMB – Lightweight Wall Firebatt 30M - CID (UKCA)

FDMB – Lightweight Wall Firebatt 30M - CID (UKCA)

FDMB – Lightweight Wall Firebatt 60M - CID (UKCA)

FDMB – Lightweight Wall Firebatt 60M - CID (UKCA)

FDMB – Lightweight Wall Firebatt 90M - CID (UKCA)

FDMB – Lightweight Wall Firebatt 90M - CID (UKCA)

FDMB – Lightweight Wall Gypsum - CID (UKCA)

FDMB – Lightweight Wall Gypsum - CID (UKCA)

FDMB – Remote - Lightweight Wall - CID (UKCA)

FDMB – Remote - Lightweight Wall - CID (UKCA)

FDMB – Remote - Solid Wall - CID (UKCA)

FDMB – Remote - Solid Wall - CID (UKCA)

FDMB – Shaftwall - CID (UKCA)

FDMB – Shaftwall - CID (UKCA)

FDMB – Slab Firepro - CID (UKCA)

FDMB – Slab Firepro - CID (UKCA)

FDMB – Solid Wall Firebatt - CID (UKCA)

FDMB – Solid Wall Firebatt - CID (UKCA)

FDMB – Solid Wall Firepro - CID (UKCA)

FDMB – Solid Wall Firepro - CID (UKCA)

FFDM – Technical specifications (137/19)

FFDM – Technical specifications (137/19)

Similar products from Mandik UK Limited

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm)  - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper